"Parameter setting" mode
Circuit breaker may trip.
If the trip settings are changed while the breaker is closed (and under load) the breaker may trip.
Adjust parameters only when the circuit breaker is in the open position.
In this mode, the following parameters can be adjusted:
- load shedding
- load restore
- delay time for load shedding/load restore
- language setting for display
To access "Parameter setting" mode, press the following button(s):
In "Autoscroll" mode
Screens displayed in "Parameter setting" mode
Screen 1
Change Parameters
Load.Shed..=.0000.A
=+
=-
.und. =Confirm
Screen 2
Change Parameters
Load.Restore=.0000.A
=+
=-
.und. =Confirm
Screen 3
Change Parameters
tx..........=...00.s
=+
=-
.und. =Confirm
Screen 4
Change Parameters
Sprache/Lang=...XXXX
=+
=-
.und. =Confirm
Screen 5
Changed.Parameter
being.saved,
wait.10s
NOTE
When screen 1, 2, 3 or 4 is displayed and no key is pressed within 10 seconds, "Parameter setting" mode is canceled.
Any parameter changes performed are not accepted. Display switches back to "Autoscroll" mode
NOTICE
Setting
Load shedding
Setting
Load restore
Setting
Delay time 
Load shedding/load restore
Setting
Display language
XXXX may be ENGL or GERM
Parameter settings are being
changed, switches to "Auto-
scroll" mode after 10 seconds
9 – 25