Labels; Circuit Breaker Frame Accessory Label; Circuit Breaker Frame Type Label - Siemens UL 489 Operating Instructions Manual

Hide thumbs Also See for UL 489:
Table of Contents

Advertisement

2

Labels

2.1

Circuit breaker frame accessory label

(with terminal designations)
Charging Motor
1st Shunt Trip
X5-1 (-)
240
VAC
X6-13 (-)
X5-2 (+)
250
VDC
X6-14 (+)
Remote Close Coil
UVR
X6-7 (+)
120
VAC
X5-11 (-)
X6-8 (-)
125
VDC
X5-12 (+)
Siemens Industry, Inc
Grand Prairie, TX 75050, USA
2.2

Circuit breaker frame type label

A
Circuit breaker
B
Non-automatic switch
(1)
UL-Mark (for circuit switch applied by a white sticker, within the shown frame)
(2)
Maximum rated current
(3)
Rated operating voltages
(4)
Rated frequency
(5)
Rated short-circuit breaking capacity
(6)
Necessary overcurrent protection
(7)
Enclosure size
(8)
Installation space
(9)
Main connections
(10)
Switch mark
2 – 1
2nd Shunt Trip
240
VAC
X9-1 (-)
VAC
250
VDC
X9-2 (+)
VDC
Remote Reset
120
VAC
X8-13 (-)
120
VAC
125
VDC
X8-14 (+)
125
VDC
Ready to Close Switch
UVR Switch
X6-5
240 VAC
X9-10
240 VAC
X6-6
4 A
X9-11
3 A
1st Shunt Trip Switch
Open Fuse Switch
X9-7
240 VAC
X9-5
240 VAC
X9-8
3 A
X9-6
5 A
Made in Czech Republic / Assembled in USA
A
Amps Max.
3000 A
Volts Max
600 AC
Frequency
50/60 Hz
Interrupting Rating
Max RMS Symmetrical
480 V
100 kA
600V
85 kA
Suitable for continous operation
at 100% of rating only if used
in a minimum cubicle space
22 (Width) by 22,5 (Hight) by
19,5 (Depth) inches.
Use insulating liner on top of
cubicle, above arc chutes.
For Use With Bus Connection Only.
ID-No.
31910220089
52a
1st Aux. SW.
52b
X6-3
X6-11
X6-1
X6-4
X6-12
X6-2
52a
2nd Aux. SW.
52b
X5-5
X5-9
X5-3
X5-6
X5-10
X5-4
240 VAC ,
10 A / 125 VDC ,
0.5 A / 24 VDC ,
B
(1)
LISTED
Molded Case Switch
11FZ
3-pole unit
Amps Max.
(2)
Volts Max
600 AC
Frequency
50/60 Hz
(3)
This switch is suitable for use
(4)
on a circuit capable of
delivering not more than
, rms symm. 480 VAC
(5)
, rms symm. 600 VAC
when protected by branch
circuit type fuses or Ckt. Bkr.
(6)
with the same ampere rating.
Suitable for continous operation
(7)
at 100% of rating only if used
in a minimum cubicle space
(Width) by
(Hight) by
(Depth) inches.
(8)
(9)
ID-No.
Bell Alarm
X6-9
240 VAC
X6-10
5 A
X9-12
X9-14
X5-7
X5-8
RESET
TRIPPED
X9-13
3A
(BELL ALARM SHOWN TRIPPED)
0131
(10)