HART Multiplexer System KFD*-HM*-16
Appendix
Command
Action
Read dynamic data of up to 7
transmitters.
135
Read SCAN status of up to 31
136
transmitters.
Write SCAN status of up to 31
137
transmitters.
Read cumulative responses of up to
138
27 transmitters.
Reset cumulative responses of up to
139
35 transmitters.
Read transmitter counts of tries and
140
failures of up to 16 transmitters.
Reset transmitter counts of tries and
141
failures of up to 16 transmitters.
Read counts of host
142
communications.
Reset counts of host
143
communications.
144
Read retry limits.
Write retry limits.
145
146
Read the selected SCAN command.
147
Select SCAN command.
148
Read SCAN status.
Write SCAN status.
149
150
Read Master type (gender).
151
Write Master type (gender).
152
Read loop search type.
Write search type.
153
154
"Rebuild" up to 83 loops.
Pass through host command to
155
transmitter and transmitter response
to host.
Meaning
For the given long frame addresses the function returns the
following transmitter data:
• The selected SCAN command
• Long frame address
• HART data
For the given long frame addresses, this command returns
the SCAN status of the transmitters (0 = SCAN disabled, 1 =
SCAN enabled).
For the given long frame addresses, this command sets the
SCAN status of the transmitters (0 = disable SCAN,
1 = enable SCAN).
This command returns the OR-combination of
communication errors and status response bits.
This command resets the cumulative responses.
Communication statistic that contains the number of
commands sent to the transmitter and the number of
commands that failed.
Reset the communication statistic.
Communication statistic concerning the Multiplexer.
Reset the communication statistic.
Retries in case of "Busy": 0 ... 11 (default is 0),
Retries in case of communication errors: 0 ... 11
(default is 2).
During SCAN the HART commands 1, 2 or 3 (see above)
can be executed.
With these commands the status of the SCAN function is set
or read, respectively (see section 8.4).
0: SCAN function disabled (default after power-up)
1: Normal SCAN function activated
2: Special SCAN function activated (see 158, 159)
1 = Primary Master (default),
0 = Secondary Master.
The loop search type defines the polling address(es) for a
transmitter that did not respond during several requests
(disappeared) is searched (see also command 129).
0: Single transmitter, 4 mA ... 20 mA (single analogue)
(only polling address 0) (default)
1: Single transmitter, unknown (single unknown)
(first one of the polling addresses 0 to 15)
Note: The search procedure without any connected
transmitters is 16 times longer because all 16 polling
addresses are checked!
2: Reserved for multidrop
see section 7.1.5.
By this any command can be passed to a field device and
the response can be evaluated - without any modification by
the Multiplexer.
59