Pepperl+Fuchs KFD HM 16 Series Manual page 54

Hart multiplexer system
Table of Contents

Advertisement

HART Multiplexer System KFD*-HM*-16
Diagnosis and fault elimination
Description
Code
2
Invalid selection
The parameter value was too
3
large
The parameter value was too
4
small
Too few data bytes received
5
Warning
8
9
1st parameter too large
11
2nd parameter too large
Access restricted
16
Too many items requested
17
Warning
31
Busy
32
Command not implemented
64
65
Not specified
54
The following response codes can occur on the Multiplexer:
Meaning
The selected code/index is not permissible.
The message has no error, but it contains
fewer bytes than expected for the execution of
the command.
Here (132): Preamble length not within range
5 ... 20 and has been set to 5 or 20.
The first of the two parameters is too large.
The second of the two parameters is too large.
The command has been ignored, since the
current device status does not permit the
command to be carried out correctly.
Here (137): SCAN value has not been
changed, since it is identical.
The device is executing a function, which
cannot be interrupted by this command.
The command does not exist and therefore
cannot be executed.
This error message is also output if an error
occurs that cannot be accurately specified by
the device.
Parameter not in the permissible range.
Can occur with
commands ...
147, 149, 151, 153
59, 129, 155
59
17, 18, 59, 129 ... 141,
145, 147, 149, 151,
153, 154, 155, 157
132
145
145
6, 17, 18, 38, 41, 42,
48, 59, 106, 128 ... 157
131, 132, 133,
135 ... 141, 154
137
6, 17, 18, 38, 41, 42,
59, 106, 128,
130 ... 157
almost all
132, 137