HART Multiplexer System KFD*-HM*-16
Configuration
Parameterizing of the communication
Double-Click in the project window with mouse button on Multiplexer.
Open the Communication menu.
The Communication menu is used to set the communication parameters between
the HART Multiplexer and the field device.
The following parameters are adjustable:
•
•
•
Figure 6.8
The Communication window is indicated.
Retries on "Busy": Repeat attempts to establish a communication with the field
device, if the field device transmits Busy.
Retries on error: Repeat attempts to establish a communication with the field
device, if an error occurs.
Searchmode: Here the mode is determined which is used to search for other
devices:
–
single analog: The HART Multiplexer uses only poll address 0 to search for
connected devices.
–
single unknown: The HART Multiplexer searches for all short addresses
between 0 and 7 and identifies the first device which responds.
Communication window
37