4.21.5

Converter operation on a grounded network

NOTICE
Damage resulting from protective conductor currents
When the machine is operated with a converter with current limiting, but without ground-fault
monitoring, protective conductor currents of up to 1.7 times the phase conductor current can
flow if there is a ground fault on the output side. Neither the PE conductors of normally rated
multi-conductor connecting cables nor the PE connecting points of standard terminal boxes is
suitable for this purpose. Material damage can result.
● Use an appropriately sized PE conductor.
● Connect the PE conductor to the grounding terminal on the motor enclosure.
54
SIMOTICS FD 1LN1
Operating Instructions 01/2019