Converter Operation On A Grounded Network; Insulated Bearings When Operating The Converter; Figure 4-2 Schematic Representation Of A Single Drive - Siemens SIMOTICS 1PQ8 Operating Instructions Manual

Low-voltage motor
Table of Contents

Advertisement

Note
Converter documentation
The operating instructions for the converter are not part of this documentation. Refer also to
the configuration information for the converter.
4.17.5

Converter operation on a grounded network

NOTICE
Damage resulting from protective conductor currents
When the machine is operated on a converter with current limiter, but without ground-fault
monitoring, protective conductor currents of up to 1.7 times the external conductor current
can arise if there is a ground fault on the output side. Neither the PE conductors of normally
rated multi-core connecting cables nor the PE connecting points of normal terminal boxes
are suitable for this purpose. Material damage can result.
● Use an appropriately sized PE conductor.
● Connect the PE conductor to the grounding terminal on the motor enclosure.
4.17.6

Insulated bearings when operating the converter

If the machine is operated from a low-voltage converter, insulated bearings are fitted at the
NDE and an insulated encoder with insulated bearings (option).
Comply with the plates on the machine relating to bearing insulation and possible bridges.
Figure 4-2
SIMOTICS TN Series N-compact 1PQ8
Operating Instructions 11/2018
Driving machine
Motor
Coupling
Schematic representation of a single drive
4.17 Converter operation
Insulated bearings
Insulated tachometer fitting
Preparations for use
47