Electrical connection
6.5 Inserting and routing the cables
Insert the cable into the terminal box
Proceed as follows when introducing cables into the terminal box:
1. Unscrew the cable entry plate.
2. Drill the required number of holes or threads in the required size in the cable entry plate.
3. Fit the required cable glands.
4. Route the cables through the cable glands.
5. Fit the cable entry plate to the terminal box with the assembled cables.
6. Connect the ends of the cables to the terminals in accordance with the circuit diagram. The
Refer to Chapter "Connecting cables ..." for more information.
6.5.3

Laying cables

● Lay the cables in accordance with IEC/EN 60364-5-52.
● Use EMC cable glands for fixed cables. Screw the EMC cable glands into the threaded
● Use shielded cables whose shields are conductively connected to a large area of the
● In the case of aluminum connecting bars, insert a steel washer between the cable lug and
● Arrange the exposed connecting cables in the terminal box so that the PE conductor has
● Close and seal unused bushings and glands using a metal screw plug. This is the way to
6.5.4

Connecting cables with cable lugs

1. Select the cable lugs according to the required cable cross-section and fixing screw or stud
2. Remove the insulation from the conductor ends so that the remaining insulation reaches
90
Ensure that the cable entry plate can be assembled after drilling and that it features
sufficient stiffness.
circuit diagram is located in the cover of the terminal box.
holes in the entry plate, which can be unscrewed.
terminal box of the motor via EMC cable glands.
the connecting bar. This prevents contact corrosion.
excess length and the insulation of the cable strands cannot be damaged.
achieve a high frequency-proof shielding.
size. Information about the maximum cross-section for the respective standard terminal box
design can be found in the catalog.
A sloped/angular arrangement of the supply cables is only permitted provided the required
minimum air clearances are met.
almost up to the cable lug
. Connect only one conductor per cable lug.