Faults At The External Fan; Table 8-4 Cooling System Faults - Siemens SIMOTICS FD 1LN1 Operating Instructions & Installation Instructions

Low-voltage motor
Table of Contents

Advertisement

8.10.5

Faults at the external fan

The following table shows the possible causes of and remedial measures for faults on forced-
ventilated machines.
Table 8-4
Cooling system faults
↓ High temperature rise with load
Possible causes of faults
X
Wrong direction of rotation of the external fan
X
External fan is not running
X
Reduced air flow
SIMOTICS FD 1LN1
Operating Instructions 01/2019
Remedial measures
Check the electrical connections to the external fan.
Check the external fan and its connections.
Check the air ducts; clean the machine.
Operation
8.10 faults
123