If you connect two motors in series in "tandem operation", locate a coupling between the
motors; this coupling should satisfy the Directive 2014/34/EU or the regulations that apply in the
country where the equipment is installed.
4.19.6

Converter operation on a grounded network

NOTICE
Damage resulting from protective conductor currents
When the machine is operated with a converter with current limiting, but without ground-fault
monitoring, protective conductor currents of up to 1.7 times the phase conductor current can
flow if there is a ground fault on the output side. Neither the PE conductors of normally rated
multi-conductor connecting cables nor the PE connecting points of standard terminal boxes is
suitable for this purpose. Material damage can result.
● Use an appropriately sized PE conductor.
● Connect the PE conductor to the grounding terminal on the motor enclosure.
SIMOTICS FD 1MM1
Operating Instructions 02/2019
Preparations for use
4.19 Converter operation
49