Srm1(-V2) Pc Setup Settings - Omron CPM1 Programming Manual

Hide thumbs Also See for CPM1:
Table of Contents

Advertisement

1-1-4 SRM1(-V2) PC Setup Settings

Word(s)
Bit(s)
Startup Processing (DM 6600 to DM 6614)
The following settings are effective after transfer to the PC only after the PC is restarted.
DM 6600
00 to 07
Startup mode (effective when bits 08 to 15 are set to 02).
00: PROGRAM; 01: MONITOR 02: RUN
08 to 15
Startup mode designation
00: Programming Console switch
01: Continue operating mode last used before power was turned off
02: Setting in 00 to 07
DM 6601
00 to 07
Not used.
08 to 11
IOM Hold Bit (SR 25212) Status
0: Reset; 1: Maintain (See caution on page 17.)
12 to 15
Forced Status Hold Bit (SR 25211) Status
0: Reset; 1: Maintain
DM 6602
00 to 03
Program memory write-protection
0: Program memory unprotected
1: Program memory write-protected (except DM 6602 itself)
04 to 07
Programming Console display language
0: English; 1: Japanese
08 to 11
Expansion Instructions
0: Default settings; 1: User settings
12 to 15
Not used.
DM 6603
00 to 03
Maximum number of CompoBus/S devices
0: Max. no. 32
1: Max. no. 16
04 to 07
CompoBus/S communications mode setting (V2 only)
0: High-speed communications
1: Long-distance communications
08 to 15
Not used.
DM 6604
00 to 07
00: If data could not be saved for a power interruption (AR 1314 ON), a memory error will not be
generated.
01: If data could not be saved for a power interruption (AR 1314 ON), a memory error will be
generated.
08 to 15
Not used.
DM 6605 to
00 to 15
Not used.
DM 6614
Cycle Time Settings (DM 6615 to DM 6619)
The following settings are effective after transfer to the PC the next time operation is started.
DM 6615
00 to 15
Not used.
DM 6616
00 to 07
Servicing time for RS-232C port (effective when bits 08 to 15 are set)
00 to 99 (BCD): Percentage for cycle time used to service peripheral.
08 to 15
RS-232C port servicing enable
00: 5% of the cycle time
01: Use time in 00 to 07.
DM 6617
00 to 07
Servicing time for peripheral port (effective when bits 08 to 15 are set to 01)
00 to 99 (BCD): Percentage of cycle time used to service peripheral.
08 to 15
Peripheral port servicing setting enable
00: 5% of the cycle time
01: Use time in 00 to 07.
The PC Setup is broadly divided into three categories: 1) Settings related to ba-
sic PC operation and I/O processes, 2) Settings related to the cycle time, and 3)
Settings related to communications. This section will explain the settings ac-
cording to these classifications.
The following table shows the settings for SRM1(-V2) PCs in order. Refer to the
page number in the last column for more details on that setting.
Function
Section
1-1
Page
16
17
17
18
18