1-1-3 CPM2A/CPM2C PC Setup Settings

Word(s)
Bit(s)
Startup Processing (DM 6600 to DM 6614)
The following settings are effective after transfer to the PC only after the PC is restarted.
DM 6600
00 to 07
Startup mode (effective when bits 08 to 15 are set to 02).
00: PROGRAM; 01: MONITOR; 02: RUN
08 to 15
Startup mode designation
00: According to communications port setting switch and peripheral port connection
01: Continue operating mode last used before power was turned OFF.
02: Setting in 00 to 07
DM 6601
00 to 07
Not used.
08 to 11
IOM Hold Bit (SR 25212) Status at Startup
0: Reset to 0; 1: Maintain previous status
12 to 15
Forced Status Hold Bit (SR 25211) Status at Startup
0: Reset to 0; 1: Maintain previous status
DM 6602
00 to 03
Program memory write-protection
0: Program memory unprotected
1: Program memory write-protected (except DM 6602 itself)
04 to 07
Programming Console display language
0: English; 1: Japanese
08 to 11
Expansion instruction function code assignments
0: Default settings
1: User assignments
12 to 15
Not used.
DM 6603
00 to 15
Not used.
DM 6604
00 to 07
00: A memory error will not be generated if data could not be retained by the battery.
01: A memory error will be generated if data could not be retained by the battery.
08 to 15
Not used.
DM 6605 to
00 to 15
Not used.
DM 6614
Word(s)
Bit(s)
Cycle Time Settings (DM 6615 to DM 6619)
The following settings are effective after transfer to the PC the next time operation is started.
DM 6615
00 to 15
Not used.
The PC Setup is broadly divided into four categories: 1) Settings related to basic
PC operation and I/O processes, 2) Settings related to pulse output functions, 3)
Settings related to interrupts, and 4) Settings related to communications. This
section will explain the settings according to these classifications.
The following table shows the setting in order in the DM area. For details, refer to
the page numbers shown.
(See table at the bottom of this page.)
Note The startup operating mode will be as shown in the following table is bits 08 to 15
of DM 6600 are set to 00.
Peripheral port
p
p
connected to
d
Nothing
Programming
Console
Other Programming
Device
Function
Communications port setting switch
Pin 2 OFF
PROGRAM
Mode set on Programming
Console mode switch
PROGRAM (The CPM2C will
not be able to communicate
with Programming Device.)
Function
Section
1-1
Page
16
17
17
148
Pin 2 ON
RUN
PROGRAM (The CPM2C will
not be able to communicate
with Programming Console.)
PROGRAM