AlphaEclipse 3600 Series A Sign Installation Instructions (9711-8001C)
2.
On the bottom wireway door, locate the equipment identification label. On this label, find the number and
amperage of each power circuit that must be run to the sign (example below):
In this example, two 120V circuits
are required to power the sign:
• Circuit #1 = 19.4 amps
• Circuit #2 = 19.4 amps
3.
Run power wires to the wireway using waterproof conduit:
NOTE: A separate conduit must be provided for communication wires. Power and communication wires
should never be placed together in the same conduit unless the communication wires are fiber optic.
Adaptive Explains
Why is it necessary to always run two conduits to a sign?
It is not always necessary. Two conduits are only necessary when communication wire, like RS485 wire, is run to a sign
from a computer or from another sign. In these cases, one conduit would contain the sign's power wires and the other conduit
the communication wires.
If power and communication wires are put in the same conduit, there is a chance the communication wires might pick up
electrical interference from the power wires. For example, when a live power cord is placed next to a stereo speaker wire, the
interference from this cord may cause the speaker to hum. In the case of a sign, this same effect could disrupt messages sent to
the display.
On the other hand, fiber optic cable and power wires can share the same conduit because fiber optic cable is immune to
electrical interference.
Installation
CIRCUIT #1: 19.4
CIRCUIT #2: 19.4
CIRCUIT #3: NA
CIRCUIT #4: NA
CIRCUIT #5: NA
CIRCUIT #6: NA
CERTIFIED TO CSA STD.
C22.2 No. 60950-00-CAN/CSA
CONFORMS TO UL STD.
No. 60950 3RD EDITION
C
US
NEMA TYPE 3R ENCLOSURE
65801
THE DISTINCTIVE TRADE DRESS OF THIS PRODUCT IS A
TRADEMARK OF ADAPTIVE MICRO SYSTEMS LLC
Figure 2: Equipment identification label
Through top wireway
Through bottom wireway
Figure 3: Wireway conduit locations
CIRCUIT #7:
NA
MODEL NO.:
CIRCUIT #8:
NA
SERIES:
CIRCUIT #9:
NA
VOLTS:
HZ:
CIRCUIT #10: NA
AMPS:
DATE OF MANUFACTURE:
SERIAL NO.:
PARTS SERVICEABLE BY TRAINED TECHNICIANS ONLY!
DISCONNECT POWER BEFORE SERVICING
Adaptive Micro Systems LLC
Milwaukee, Wisconsin 53224 USA
Through back of
bottom wireway
September 28, 2004
1180 - 3601112032RGB
A
120 ~ VAC
60Hz
38.8 A
1/26/2004
EH0002231
17

Advertisement

Table of Contents
loading

Table of Contents