LED Operation

The Input Board uses two onboard LEDs (D1 and D2) to provide status information
during the power-up sequence as well as during normal operation.
Table 3: PW-6000 Input Module Onboard LED Settings
Mode
Power-up
sequence
Normal
Operation
In addition to the status LEDs, there are two additional relay status LEDs and 16 input
status LEDs on board. The input LEDs flash when there is an alarm associated with
the input. When any relay or input is energized or ON, its corresponding status LED
becomes ON also. The LED remains ON for as long as the relay is energized.
PW-6000 Input Module Installation Guide, Document 800-01952, Revision B
LED D1
LED D2
ON
OFF
OFF
ON
ON
ON
FLASH
ON
FLASH
FLASH
Installing the PW-6000 Input Module
Description
Start power-up, hardware setup.
Testing RAM.
Testing ROM and completing
initialization.
LED D1 flashes four times after
power-up is completed.
This is the processor heartbeat LED. It
flashes once every second. A short ON
time (~20% duty cycle) indicates the
board is offline or has lost serial
communication with the Controller
board. A long ON time (~80% duty
cycle) indicates the board is online and
communicating with the Controller
board.
Flash when there is activity on its Serial
Port.
LED Operation
5