Step 2
PRIOR TO BEGINNING THIS PROCEDURE,
a preliminary examination of the appliance
and the automatic intermittent pilot system
should be made to determine that the
automatic intermittent pilot system can
be properly applied to the appliance.
This procedure is intended as a guide to aid in
safely installing a listed automatic intermittent
pilot system on an existing listed appliance
equipped with an atmospheric gas burner(s) &
not of the direct vent type.
This procedure is based on the assumption
that the history of the specific installation has
been one of safe and satisfactory operation.
This procedure is predicated on central
furnace and boiler installations, and it should be
recognized that generalized procedures cannot
anticipate all situations. Accordingly, in some
cases deviation from this procedure may be
necessary to determine safe operation of the
equipment.
Step 3
• The input rating of the system must be
equal to or greater than the name plate
input rating of the appliance.
• The existing pilot burner shall be used or
if it must be replaced, it shall be replaced
with an identical model located in the same
mounting as the original pilot.
• If electronic components are installed in an
area subject to water then means shall be
provided to protect components.
SAFETY INSPECTION PROCEDURE PER ANSI Z21.71;
EXHIBIT B: Procedure for installing automatic intermittent pilot systems.

INSTALLATION

The following steps should be followed
in making the modifications:
1. Perform a safety inspection of the existing
appliance installation.
See Exhibit A (pg 6) for a recommended
procedure for such a safety inspection.
2. Shut off all gas and electricity to the appliance.
To shut off gas use the shutoff valve
in the supply line to the appliance. If
a manual gas valve is not in the gas
supply line within 6 feet (1.83 mm) of the
appliance in an accessible location one
shall be installed. Do not use the shutoff
valve which is provided as part of a
combination control.