Important notes:
If the UPS is used in single mode, J1 and J2 must be connected.
If the UPS is used in parallel mode, the Jumper between J1 and J2 must be
removed.
9)
It is requested to use the accessorial terminal splices which can be compacted
on the wires tightly, to ensure the connection between the wires and the
terminal block is reliable.
10) Install an output breaker between the output terminal of UPS and the load, and
the breaker should be with leakage current protective function if necessary.
11) Turn off all the loads first before connecting the load with the UPS, then
perform the connection and finally turn on the loads one by one.
12) After completing the installation, please check the wires to make sure all were
connected correctly and tightly.
13) Suggest charging the batteries for 8 hours before use. After Installation, turn
on the mains power switch and turn the input breaker in the "ON" position, the
UPS will charge the batteries automatically. It can also use the UPS
immediately without charging the batteries, but the backup time may be less
than the standard value.
14) If it is necessary to connect the inductance load such as a monitor or a laser
printer to the UPS, the start-up power should be used for calculating the
capacity of the UPS, as its start-up power consumption is too big to make the
UPS which capacity is small fail easily.

4.3. External Battery Pack Connecting Procedure

1. The nominal DC voltage of external battery pack is 240Vdc. To achieve longer
backup time, it is possible to connect multi-battery packs, but the principle of
"same voltage, same type" should be strictly followed.
2. For OLS6000E(XL), select the UL1015 10AWG (6mm² ) respectively or other
insulated wire which complies with AWG Standard for the UPS battery wirings.
3. For OLS10000E(XL), select the UL1015 8AWG (10mm² ) respectively or other
insulated wire which complies with AWG Standard for the UPS battery wirings.
4. The external battery pack must be independent for each UPS. It is forbidden
that two UPS use one external battery pack.
5. The procedure of installing battery pack should be complied with strictly.