CyberPower OLS6000E User Manual page 13

Table of Contents

Advertisement

2)
No matter the UPS is connected to the mains power or not, the output of the
UPS may be electrically live. The parts inside the unit may still have hazardous
voltage after turning off the UPS. To make the UPS have no output, turn off the
UPS, and cut off the mains power supply, wait the UPS shut down completely,
finally cut off the battery connection.
3)
Open the terminal block cover located on the rear panel of UPS, please refer
to the appearance diagram.
4)
For OLS6000E(XL), it is recommended to select the UL1015 10AWG (6mm² )
or other insulated wire which complies with AWG Standard for the UPS input
and output wirings.
5)
For OLS10000E(XL), it is recommended to select the UL1015 8AWG (10 mm² )
or other insulated wire which complies with AWG Standard for the UPS input
and output wirings.
6)
Ensure the capacity of mains power supply. Do not use the wall receptacle as
the input power source for the UPS, as its rated current is less than the UPS's
maximum input current. Otherwise the receptacle may be burned and
destroyed.
7)
The protective earth ground wire should be installed first according to the
following diagram. It is better to use green wire or green wire with yellow ribbon
wire.
8)
Connect other input and output wires to the corresponding input and output
terminals according to the following diagram.
Note: Make sure that the input and output wires and the input and output terminals
are connected tightly.
INPUT
Input Ground
Input N
Input L
Battery+
Battery-
Battery Ground
Fig.4-2 Input and output Terminal Block wiring diagram
BATTERY
N
L
+
-
JUMPER
OUTPUT
J1
J2
N
10
L
Output Ground
Output L
Output N
Parallel Jump 2
Parallel Jump 1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ols6000exlOls10000exlOls10000e