Cyber Power Systems, Inc.
www.cyberpower.com
User's Manual
O L S 6 0 0 0 E R T 6 U A
O L S 1 0 0 0 0 E R T 6 UA
K01-C000653-00

Advertisement

Table of Contents
loading

Summary of Contents for CyberPower OLS6000ERT6UA

  • Page 1 User’s Manual O L S 6 0 0 0 E R T 6 U A O L S 1 0 0 0 0 E R T 6 UA Cyber Power Systems, Inc. www.cyberpower.com K01-C000653-00...
  • Page 3: Table Of Contents

    TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS ....................1 UNPACKING ............................3 HARDWARE INSTALLATION ......................6 RACKMOUNT INSTALLATION ........................6 VERTICAL/TOWER INSTALLATION ......................8 OVERVIEW ............................1 0 POWER MODULE FRONT/REAR PANEL DESCRIPTION ..............1 0 BATTERY MODULE FRONT/REAR PANEL DESCRIPTION ............1 BATTERY MODULE CONNECTION ......................1 2 ELECTRICAL INSTALLATION ......................
  • Page 4: Important Safety Instructions

    IMPORTANT SAFETY INSTRUCTIONS This manual contains important instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate the UPS. Installation • This is permanently connected equipment, and it must be installed by qualified maintenance personnel.
  • Page 5 IMPORTANT SAFETY INSTRUCTIONS Maintenance, Servicing and Faults • Do not remove the enclosure since the UPS operates with hazardous voltages. It is to be serviced only by qualified maintenance personnel. • Caution! Risk of electric shock. Even after the unit is disconnected from the mains power supply (building wiring terminal) components inside the UPS are still connected to the battery which are potentially dangerous.
  • Page 6: Unpacking

    UNPACKING Package List The package should contain the following items. Box of Power Module See page 4 for details Box of Battery Module See page 5 Inspect the contents upon receipt. Do not turn on the unit and notify the carrier and the dealer immediately if there is any damage or lacking of some parts.
  • Page 7 Binding Head Screws: Plastic Screw Hole Dust M4X8L (6) Washers (8) Covers (8) Parallel Cable Rackmount Ears Battery Cable Terminal (9) (Stands) PowerPanel® Business software is available on our website. Please visit www.cyberpower.com and go to the Software Section for free download.
  • Page 8 UNPACKING The box of Battery Module should contain the following items: Battery Module Rackmount Rails Flat Head Screws: Pan Head Screws: M5 Nut (8) Binding Head Screws: M4X8L (8) M5X12L (12) M4X8L (6) Plastic Screw Hole Dust Terminal (6) Rackmount Ears Washers (8) Covers (12) (Stands)
  • Page 9: Hardware Installation

    HARDWARE INSTALLATION These versatile UPS systems can be mounted in a rackmount or vertical tower orientation. This versatility is especially important to growing organizations with changing needs that value having the option to position a UPS on a floor or in a rackmount system. Please follow the instructions below for the respective mounting methods.
  • Page 10 HARDWARE INSTALLATION Step 2: Rackmount rails Installation (1) The rails adjust to mount in 48-cm (19-inch) panel racks from 46.4 to 73.8cm (18.3 to 29 inches) deep. Select the proper holes in the rack for positioning the UPS in the rack. The rails take up position 1 through position 3.
  • Page 11: Vertical/Tower Installation

    HARDWARE INSTALLATION VERTICAL/TOWER INSTALLATION Step 1: Rotate the Multifunction LCD Module ( 1 ) Unscrew the right panel of the UPS. Separate the right panel from the UPS. (2) Unscrew the LCD plate; gently lift the LCD module out. Rotate it to the tower orientation Reinstall it for a tower configuration.
  • Page 12 HARDWARE INSTALLATION Step 2: Attach the base stands (1) Tighten the screws (M4X8L*8pcs) of the base stands (rackmount ears) onto the bottom of Power module and Battery module. (2) Insert dust cover into the rackmount ear screw holes that are not being used.
  • Page 13: Overview

    OVERVIEW POWER MODULE FRONT/REAR PANEL DESCRIPTION Power Module front panel Power Module rear panel 1 . LED Indicators 2. UPS Status / Multifunction LCD Readout 3. Function Buttons 4. Intelligent Slot 5. Parallel Port 6. USB Port 7. Serial Port 8.
  • Page 14: Battery Module Front/Rear Panel Description

    OVERVIEW BATTERY MODULE FRONT/REAR PANEL DESCRIPTION Battery Module front panel Battery Module rear panel 1. On-board Replaceable Fuse Cover Replaceable fuse is accessible from the rear panel. It must be done by qualified personnel. 2. Output Connector Use this output connector to connect the Battery module and the Power module. 3.
  • Page 15: Battery Module Connection

    OVERVIEW BATTERY MODULE CONNECTION Loosen the screws to remove the Terminal Block Cover on the rear panel of Power module. Connect the Battery Cable to the Power module and check if the polarity is correct. Loosen the screws to remove the Output Connector Cover of Battery module. Connect the Battery Cable to the Battery module.
  • Page 16: Electrical Installation

    ELECTRICAL INSTALLATION POWER WIRES INSTALLATION • The system must be installed and wired only by qualified electricians in accordance with applicable safety regulations. • For safety, please cut off the mains power switch before installation. • When installing the electrical wiring, please note the nominal amperage of your incoming feeder.
  • Page 17 ELECTRICAL INSTALLATION (2) No matter the Power module is connected to the mains power or not, the output of the Power module may be electrically live. The parts inside the unit may still have hazardous voltage after turning off the Power module. To make the Power module without output, turn off the Power module, and cut off the mains power supply, wait the Power module shut down completely, finally remove the battery connection.
  • Page 18: Epo Connection

    ELECTRICAL INSTALLATION Important notes: If the Power module is used in single mode, the output must be connected to sL and sN. If the Power module is used in parallel mode, the output must be connected to pL and pN. (10) Install an output breaker between the output terminal of Power module and the load.
  • Page 19: Ups System Startup

    Check all the connection and DC voltage of battery pack output are correct. Turn on the input breaker, and the fan begins to rotate. "CyberPower" will be shown on LCD screen first. The default UPS status summary will be shown on LCD screen.
  • Page 20: Operation

    The UPS is equipped with five-button, dot matrix LCD and four colorized LED to provide the function settings and information display. During powering on, the LCD would display the “CyberPower” for several seconds and then enter to the default page which shows the UPS status summary.
  • Page 21: Operating Modes

    OPERATION OPERATING MODES DISPLAY MODE DESCRIPTION MODE NORMAL BATTERY BYPASS FAULT Line UPS is operating in Line Mode. The UPS is Mode operating and protecting the equipment normally. NORMAL BATTERY BYPASS FAULT When the mains power is abnormal, the UPS will transfer to battery mode, the necessary energy is provided by the battery, the buzzer Battery...
  • Page 22 OPERATION OPERATING MODES DISPLAY MODE DESCRIPTION MODE ECO mode could be set through the <UPS setting menu - Power Strategy> in Bypass mode. When UPS is operating in ECO mode, the power NORMAL BATTERY BYPASS FAULT for the load is directly supplied from the mains power via internal filter while the utility power is in normal range, the efficiency will up to 96% to save power for the user and the equipment...
  • Page 23: Lcd Function Tree

    OPERATION LCD FUNCTION TREE Main Page Status Load Capacity Input Voltage Battery Voltage UPS Status Output Parameter Input Parameter Bypass Parameter Power Parameter Battery Parameter Events Control Input Password **** Buzzer Mute Events Type/Model Alarm Serial Number Clr EPO Status Fault Battery Test Rating...
  • Page 24 OPERATION STATUS There are 12 types of UPS status readout available for display. Press “UP” and “DOWN” buttons to scroll through the “Status” menu shown in the table below. UPS STATUS ITEM DATA DISPLAYED DESCRIPTION Volt: X.X V Displays the Output Voltage Output Parameter Curr: X.X A Displays the Output Current...
  • Page 25 OPERATION Enter SUB-MENU (CONTROL, SETTING, EVENTS, and ID) Press “ESC” button to enter sub-menu. Press “UP” and “DOWN” buttons to scroll through CONTROL, SETTING, EVENTS, and ID menu. Press the “ENTER” button to enter to the selected menu. NORMAL BATTERY BYPASS FAULT SUB-MENU (CONTROL, SETTING, EVENTS, and ID)
  • Page 26 OPERATION SETTING Menu Select “Setting” and press “ENTER” button. Press “UP” and “DOWN” buttons to scroll through the “Setting” menu shown in the table below. Press “ENTER” button to enter the setting page. Press “UP” and “DOWN” buttons to scroll through the setting value. Press “ENTER”...
  • Page 27 OPERATION EVENTS Menu The UPS will record the 30 most recent system events/alarms/faults in event logs. Select “Events” and press “ENTER” button. Press “UP” and “DOWN” buttons to scroll through the “Events” menu shown in the table below. Press “ENTER” button to enter the next page. Press “UP”...
  • Page 28 OPERATION ID Menu Select “ID” and press “ENTER” button. Press “UP” and “DOWN” buttons to scroll through the “ID” menu shown in the table below. Press “ENTER” button to enter the next page. Press “UP” and “DOWN” buttons to scroll through the ID items. Press “ENTER”...
  • Page 29: Parallel Function

    OPERATION PARALLEL FUNCTION Brief Introduction N represents the minimum UPS number that the total load needs, X represents the redundant UPS number, i.e. the fault UPS number that the system can handle simultaneously. When the X is larger, the reliability of the power system is higher. Up to 4 UPS can be connected in parallel to achieve output power sharing and power redundancy.
  • Page 30 OPERATION BATTERY INPUT~ OUTPUT~ 1#Battery pack OUTPUT~ BATTERY INPUT~ 2#Battery pack To Main Output To Main Input Breaker Breaker Input and output terminal block wiring diagram TO UTILITY Main Maintenance Bypass Switch Main Input Breaker Main Output Breaker TO LOAD Parallel installation diagram...
  • Page 31 OPERATION 8. The distance between the UPS in parallel and the breaker panel is required to be less than 20 meters. 9. The difference between the wires of input and output of the UPS is recommended to be less than 2 meters. 10.
  • Page 32 OPERATION How To Remove A Single UPS From A Parallel System First, the parallel system must be installed one main maintenance bypass switch. Ensure the bypass of the parallel system is normal and the bypass setting is "enable". Press the “ON/OFF” button of one UPS, each UPS would turn off and transfer to the Bypass mode.
  • Page 33: Troubleshooting

    TROUBLESHOOTING Warning Indication PROBLEM POSSIBLE CAUSE SOLUTION DISPLAYED EPO Active EPO connector is open Check the EPO connector status The Ground wire is disconnected or Phase Check the Ground wire status. Site Fail and neutral conductor at Reverse mains power wiring. input of UPS system are reversed Do the battery test.
  • Page 34 TROUBLESHOOTING PROBLEM POSSIBLE CAUSE SOLUTION DISPLAYED The UPS with different power strategy There are different power setting (Ex. one Line mode and one Work Mode Differ strategies setting in Converter mode) are forbidden to parallel system parallel. The UPS with different capacity (Ex. one There are different UPS Rate Power Differ XRT6-6000(L) and one XRT6-10000(L)
  • Page 35 TROUBLESHOOTING Others PROBLEM POSSIBLE CAUSE SOLUTION DISPLAYED No indication, no warning tone even Check the building wiring and input though system is No input voltage cable. Check if the input breaker is connected to mains closed power supply BYPASS LED light up even though the Inverter not switched on Press “ON/OFF”...
  • Page 36: Battery Maintenance

    BATTERY MAINTENANCE BATTERY MAINTENANCE • Battery replacement should be performed by qualified personnel. • The batteries used for battery pack are value regulated sealed lead-acid maintenance free battery. Please charge the UPS regularly in order to maximize the expected life of the battery.
  • Page 37: Technical Specifications

    TECHNICAL SPECIFICATIONS Models OLS6000ERT6UA OLS10000ERT6UA Capacity (VA) 6000 10000 Capacity (Watts) 5400 9000 Form Factor Rackmount/ Tower Input Phase Single Voltage Range 110~276Vac (Depends on load level) Frequency Range 50/60±10%Hz Rated Current Power Factor ≥ 0.99 @ full load Battery...
  • Page 39 Cyber Power Systems, Inc. www.cyberpower.com 11F., No.26, Jinzhuang Rd., Neihu Dist., Taipei City 114, Taiwan Entire contents copyright © 2020 Cyber Power Systems, Inc., All rights reserved. Reproduction in whole or in part without permission is prohibited. PowerPanel® Business and PowerPanel® Personal are trademarks of...