3.11.2 Parameter to be downloaded to the input module WDI100

3.12 Commissioning of Communication

Wireless Proximity Switches / Issue: 09.2004
At each start-up of a field bus node or of the whole system, parameters are downloaded to the
WDI100 field bus slave. The parameters contain the Cell-ID and one bit per possible wireless
proximity switch. The bit will be "1" if a sensor is configured, "0" if not used in this configuration.
The structure is:
Parameter
Cell-ID
Sensors
16 ...
1
Sensors
32 ... 17
Sensors
48 ... 33
Sensors
64 ... 49
Sensors
80 ... 65
Sensors
96 ... 81
Sensors
112 ... 97
Sensors
120 ... 113
These parameters have to be set within the configuration software
of the automation system / PLC.
If the SET menue parameter "CFG LOCAL/FB" is set to "FIELDBUS", the locally stored
configuration will be overwritten at the next sartup of the system (e. g. also with "0")
Assumption: The WPS Power Supply is already commissioned (compare chapter 4.4).
Installation
Mount Input Module WDI100
Mount antennas
Install and connect antenna cables
Connect Input Module to 24Vdc
Plug-in FieldBusPlug at WDI100
Ensure Supply of FieldBusPlug
Connect communication modules WSIX100 to the sensor heads
Switch on magnetic power supplies WPU100
Configuration of connection to PLC/FBP
Copy the ABB*.gsd -file for the field bus plug into the GSD subdirectory of the host
software (ABB*.gsd see engineering package WEP100.0101 1SAJ900091R0101.ZIP)
Start the host software, (or actualize the directory to choose the *.gsd file from in the
host software)
Map the wireless input module into the field bus network (assign field bus address)
In the host software, select the WDI100 as the I/O for that node and set I/O addresses
Settings of Input Module WDI100
SET-Menu
-
Set field-bus-address on WDI
-
Set Cell-ID, set the desired ID-number for this Cell (1-60)!
-
Set "Fieldbus" to LOCAL
Configuration of Sensors
CFG-Menu: Configure Sensors in the CFG Menu
-
Select a sensor address,
-
Press Button at communication module WSIX100 of selected Sensor
RUN-Mode: Check correct Sensor function
Allowed Values
0 -
60
0 - 65535
0 - 65535
0 - 65535
0 - 65535
0 - 65535
0 - 65535
0 - 65535
0 - 65535
Planning and Installation Guidelines
39