StorNext QM1200, QS1200 or QS2400 Base System - Replacing a Controller Battery
6.
Did this action correct the problem?
Yes – Go to step 7.
—
No – If the problem is not resolved, contact your Customer and Technical Support representative.
—
7.
Using the LEDs and the storage management software, check the status of all of the trays in the storage array.
8.
Does any component have a Needs Attention status?
Yes – Click the Recovery Guru toolbar button in the Array Management Window, and complete the recovery
—
procedure. If the problem is not resolved, contact your Customer and Technical Support representative.
No – Go to step 9.
—
9.
Remove the antistatic protection.
10. Gather support data about your updated storage array by using one of these methods:
Use the storage management software to collect and save a support bundle of your storage array. From the
—
Array Management Window, click Monitor >>Health >> CollectSupport Data. Then name and specify a
location on your system where you want to store the support bundle.
Use the CLI to run the save storageArray supportData command to gather comprehensive support
—
data about the storage array. For more information about this command, see Command Line Interface and
Script Commands.
NOTE Running this command can temporarily impact performance on your storage array.