Quantum StorNext QS1200 Site Planning Manual

Hide thumbs Also See for StorNext QS1200:
Table of Contents

Advertisement

Quick Links

Site Planning Guide
Quantum StorNext
QS1200/QS2400/QD6000/QD7000
6-68265-01 Rev A

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the StorNext QS1200 and is the answer not in the manual?

Questions and answers

Summary of Contents for Quantum StorNext QS1200

  • Page 1 Site Planning Guide Quantum StorNext QS1200/QS2400/QD6000/QD7000 6-68265-01 Rev A...
  • Page 2 StorNext QXS Storage Site Planning Guide, 6-68265-01 Rev A, May 2015, Product of USA. ©2015 All rights reserved. Quantum, the Quantum logo, DXi, Scalar and StorNext are registered trademarks of Quantum Corporation and its affiliates in the United States and/or other countries. All other trademarks are the property of their respective owners.
  • Page 3: Table Of Contents

    Contents About this guide ............ix Intended audience .
  • Page 4 QD6000/QD7000 Base System Airflow/Heat Dissipation and Power Requirements ....16 Airflow and Heat Dissipation ............16 Power Requirements .
  • Page 5 Figures 1 QS1200 Base System (front) ............1 2 QS2400 Base System (front) .
  • Page 6 Site Planning Guide...
  • Page 7 Tables 1 Document conventions6 1 Document conventions ............. . x 2 QS1200/QS2400 Base System Weight .
  • Page 8 viii Site Planning Guide...
  • Page 9: About This Guide

    About this guide This guide includes information about the supported controllers and drive trays as well as key specification information for each one. Use this guide to prepare your site for the installation of controllers and drive trays into an industry standard cabinet. The storage products include: •...
  • Page 10: Document Conventions And Symbols

    Document conventions and symbols Table 1 Document conventions Convention Element Blue text Cross-reference links and e-mail addresses Blue, underlined text Web site addresses Bold text • Key names • Text typed into a GUI element, such as into a box •...
  • Page 11: Qs1200 And Qs2400 Systems

    Chapter 1 QS1200 and QS2400 Systems This chapter provides specifications for the QS1200 and QS2400 systems. QS1200 and QS2400 Base System Components The QS1200 and QS2400 base systems use high-density SAS 2.0 (6-Gb/s) drive enclosure available in a rack-mount model. The QS1200 system has a capacity of twelve 3.5-in. SAS drives. The QS2400 system has a capacity of twenty-four 2.5-in.
  • Page 12: Qs2400 Base System Front View

    QS2400 Base System Front View Figure 2 provides a front view of the QS2400 base system. Figure 2 QS2400 Base System (front) End caps (the Left End Cap Has the Controller-Drive Tray Summary LEDs) Disk drives QS1200/QS2400 Base System Rear View Figure 3 provides a rear view of the QS1200/QS2400 base system.
  • Page 13: Qs1200/Qs2400 Base System Dimensions

    QS1200/QS2400 Base System Dimensions This section provides dimensions for the QS1200 and QS2400 base system. QS1200 Base System Dimensions Figure 4 provides the dimensions of the QS1200 base system. The QS1200 base system conform to the 48.3-cm (19.0-in.) rack standard. QS1200 Base System Dimensions Figure 4 QS2400 Base System Dimensions...
  • Page 14: Qs1200/Qs2400 Base System Weights

    QS1200/QS2400 Base System Weights This section provides the weight of the QS1200 and QS2400 base system and their internal components. QS1200/QS2400 Base System Weight (Max/Shipping) Table 2 provides the weight of the QS1200 and QS2400 base system. Table 2 QS1200/QS2400 Base System Weight Unit Maximum Weight Empty Weight...
  • Page 15: Qs1200/Qs2400 Base System Shipping Dimensions

    QS1200/QS2400 Base System Shipping Dimensions Table 4 provides the shipping dimensions of the QS1200 and QS2400 base system. Table 4 QS1200/QS2400 Base System Shipping Weights Unit Height Width Depth QS1200 Base System with 24.13 cm (9.5 in.) 63.50 cm (25 in.) 58.42 cm (23 in.) twelve 8.89-cm (3.5-in.) SAS disk drives...
  • Page 16: Qs1200/Qs2400 Base System Altitude Ranges

    Table 5 QS1200/QS2400 Base System Temperature and Humidity Requirements Condition Parameter Requirement Relative humidity (no Operating range (both cabinet and 20% to 80% condensation) subsystem) Storage range 10% to 90% Transit range 5% to 90% Operating gradient 10°C (50°F) per hour maximum Storage gradient 15°C (59°F) per hour maximum Transit gradient...
  • Page 17: Qs1200/Qs2400 Base System Airflow/Heat Dissipation And Power Requirements

    QS1200/QS2400 Base System Airflow/Heat Dissipation and Power Requirements This section provides airflow, heat dissipation and power requirements for the QS1200/QS2400 base system. Airflow and Heat Dissipation Allow at least 76 cm (30 in.) of clearance in front of the QS1200/QS2400 base system and 61 cm (24 in.) behind the QS1200/QS2400 base system for service clearance, ventilation, and heat dissipation.
  • Page 18: Power Requirements

    Figure 7 provides the airflow and heat dissipation of the QS2400 base system. Figure 7 QS2400 Base System Airflow 76 cm (30 in.) clearance in front of the cabinet 61 cm (24 in.) clearance behind the cabinet Power Requirements Table 7 provides the power requirements for the QS1200 and QS2400 base system.
  • Page 19: Qs1200/Qs2400 Base System Acoustic Noise Levels

    QS1200/QS2400 Base System Acoustic Noise Levels Table 8 provides the acoustic noise levels for the QS1200 and QS2400 base system. Table 8 QS1200/QS2400 Base System Acoustic Noise Levels Measurement Level Sound power 6.5 bels maximum (standby operation) Sound pressure 65 dBA maximum (normal operation) QS1200/QS2400 Base System Site Wiring and Power This section provides site wiring and power information for the QS1200 and QS2400 base systems.
  • Page 20: Ac Power Input

    AC Power Input Table 9 provides the AC power input for the QS1200 and QS2400 base systems. NOTE: Each power supply contains one 10-A slow-blow fuse. Table 9 AC Power Input for the QS1200 and QS2400 Base Systems Parameter Low Range High Range Nominal voltage 100 VAC...
  • Page 21: Qd6000 And Qd7000 Systems

    Chapter 2 QD6000 and QD7000 Systems This chapter provides specifications for the QD6000 and QD7000 systems. QD6000 and QD7000 Base System Components The QD6000 and QD7000 base systems use high-density SAS 2.0 (6-Gb/s) drive enclosure available in a rack-mount model. The systems use either high-capacity 3.5-in. SAS drives or high-performance 2.5-in.
  • Page 22: Qd6000/Qd7000 Base System Rear View

    QD6000/QD7000 Base System Rear View Figure 9 provides a rear view of the QD6000/QD7000 base system. Figure 9 QD6000/QD7000 Base System (rear) Fan Canisters Power Canisters Controller Canisters Site Planning Guide...
  • Page 23: Qd6000/Qd7000 Base System Dimensions

    QD6000/QD7000 Base System Dimensions Figure 10 provides the dimensions of the QD6000/QD7000 base system. The QD6000/QD7000 base system conform to the 48.3-cm (19.0-in.) rack standard. Figure 10 QS1200 Base System Dimensions QD6000/QD7000 Base System Weights This section provides the weight of the QD6000 and QD7000 base system and their internal components.
  • Page 24: Qd6000/Qd7000 Base System Component Weights

    QD6000/QD7000 Base System Component Weights Table 11 provides the component weights of the QD6000 and QD7000 base system. Table 11 QD6000/QD7000 Base System Component Weights Component Weight Controller canister 2.99 kg (6.60 lb) Power canister 2.5 kg (5.5 lb) Fan canister Approximately 1 kg (2.16 lb) Drive 0.74 kg (1.64 lb)
  • Page 25: Qd6000/Qd7000 Base System Altitude Ranges

    Table 13 QD6000/QD7000 Base System Temperature and Humidity Requirements Condition Parameter Requirement Relative humidity (no Operating range (both cabinet and 20% to 80% condensation) subsystem) Storage range 10% to 90% Transit range 5% to 90% Operating gradient 10°C (50°F) per hour maximum Storage gradient 15°C (59°F) per hour maximum Transit gradient...
  • Page 26: Qd6000/Qd7000 Base System Airflow/Heat Dissipation And Power Requirements

    QD6000/QD7000 Base System Airflow/Heat Dissipation and Power Requirements This section provides airflow, heat dissipation and power requirements for the QD6000/QD7000 base system. Airflow and Heat Dissipation Allow at least 81 cm (32 in.) of clearance in front of the QD6000/QD7000 base system and 61 cm (24 in.) behind the QD6000/QD7000 base system for service clearance, ventilation, and heat dissipation.
  • Page 27: Power Requirements

    Power Requirements Table 15 provides the power requirements for the QD6000 and QD7000 base system. Table 15 QD6000 and QD7000 Base System Power Requirements Component Typical Operating Power Rated Power Requirement QD6000 Base System with HIC (6-TB KVA: 1.075 KVA: 1.526 drives fully populated Watts: 1064 Watts: 1512...
  • Page 28: Ac Power Input

    NOTE: Protective ground is also known as safety ground or chassis ground. • Circuit overloading – Power circuits and associated circuit breakers must provide enough power and overload protection. NOTE: To prevent damage to the base system, isolate its power source from large switching loads, such as air-conditioning motors, elevator motors, and factory loads.
  • Page 29 NOTE: Possible risk of equipment failure – To ensure proper cooling, the base system always uses two power supplies. QD6000 and QD7000 Systems...
  • Page 30 Site Planning Guide...

This manual is also suitable for:

Stornext qs2400Stornext qd7000Stornext qd6000

Table of Contents