QXS Site Planning Guide QXS-3/4/6 Series Hybrid Storage 6-68547-01 Rev A...
Page 2
Artico, Be Certain (and the Q brackets design), DLT, DXi, DXi Accent, DXi V1000, DXi V2000, DXi V4000, DXiV-Series, FlexTier, Lattus, the Q logo, the Q Quantum logo, Q-Cloud, Quantum (and the Q brackets design), the Quantum logo, Quantum Be Certain (and the Q brackets design), Quantum Vision, Scalar, StorageCare, StorNext, SuperLoader, Symform, the Symform logo (and design), vmPRO, and Xcellis are either registered trademarks or trademarks of Quantum Corporation and its affiliates in the United States and/or other countries.
About This Guide This guide provides site planning information for the following QXS Hybrid systems: • QXS-312, QXS-324 • QXS-412, QXS-424, QXS-448, QXS-456 • QXS-648, QXS-656 Intended audience This guide is intended for storage customers and technicians. NOTE: This guide provides information for site planning at your storage location.
QXS systems. Table 1 Related Documentation For Information About Web links to download Quantum QX and QXS Storage guides listed QX and QXS Documentation Sheet* below, but not shipped with the product QX or QXS Release Notes...
Document conventions and symbols Table 2 provides document conventions and symbols. Table 2 Document conventions Convention Element Blue text Cross-reference links and e-mail addresses Blue, underlined text Web site addresses • Key names Bold text • Text typed into a GUI element, such as into a box •...
• QXS-648, QXS-656 Chassis with Bezels Installed The front of the QXS-312, QXS-324, QXS-412, QXS-424, QXS-448, and QXS-648 are all 2U high (3.5 inches/88.9mm) and use the same bezel (2U). The QXS-456 and QXS-656 are 4U high (7 inches/177.8mm) and also use the same bezel (4U). Refer to...
Chassis with Bezels Removed Figure 2 provides images of the front of the QXS-312, QXS-324, QXS-412, QXS-424, QXS-448, QXS-648, QXS-456, and QXS-656 with the bezels removed. Figure 2 Chassis Front View (Bezel Removed) 1 QXS-312 or QXS-412 Chassis 2 QXS-324 or QXS-424 Chassis •...
Page 11
Figure 3 Standard Cabinet 1 Front door 2 Rear door 3 Vertical support rails 4 Air vent Standard features of the cabinet include: • Front and rear door that can be closed and locked • Vertical rails, with mounting holes, to allow installation of storage •...
NOTE: Install the applicable storage rack on the cabinet support rails, then install the chassis/expansion storage unit, and then populate the unit with applicable drives (HDDs or SSDs). Ensure to place the cabinet in a location that allows sufficient space to maintain and service (remove and replace parts) the applicable units within the cabinet.
5 for RAID chassis and expansion chassis maximum combinations. Table 3 Cabinet Configurations Chassis Type Maximum Chassis in Cabinet Maximum Drives in Cabinet QXS-312 or QXS-412 (2U, 12 drive) QXS-324 or QXS-424 (2U, 24 drive) QXS-448 or QXS-648...
Page 14
Max Expansion System Chassis Type RAID Chassis Chassis Max Total Drives QXS-648 2U48 QXS-656 4U56 (4) & 2U12 (2) Note 1: Always consider the max drive number when mixing different chassis combinations. Note 2: It is impossible to identify all possible chassis combinations within the hybrid QXS supported configurations.
12 Drive Front Panel Components Figure 6 provides the 2U12 drive chassis (for the RAID or expansion chassis) with the bezel removed. Figure 6 2U12 Drive Chassis (Bezel Removed) Left Ear Right Ear 1 Chassis ID LED 2 Chassis status LED: Power/Activity 3 Drive status LED: Fault 4 Chassis status LED: Unit Locator 5 Chassis status LED: Fault/Service Required...
12 and 24 Drive RAID Chassis: Rear Panel Components Figure 8 provides a representative example of the drive RAID chassis (rear panel 12 and 24 components). Figure 8 12 and 24 Drive RAID Chassis: Rear Panel Components 6Gb/s CACHE LINK PORT 0 PORT 1 SERVICE−2...
12 and 24 Drive Expansion Chassis: Rear Panel Components Figure 10 provides the drive expansion chassis (rear panel components). 12 and 24 Expansion Chassis: Rear Panel Components Figure 10 SERVICE LINK LINK SERVICE LINK LINK 1 Power supplies (AC shown) 2 Expansion I/O Module A 3 Expansion I/O Module B Figure 11...
The RAID and expansion chassis designators are as follows: • 2U12 chassis (LFF): • “2U12” denotes the 3.5” QXS-312 chassis (with controller or expansion modules) • The 2U12 chassis is equipped with a drive in each drive slot • 2U24 chassis (SFF): •...
Chapter 3 QXS-4 Series Specifications This chapter provides the following information: • QXS-412/424/448 RAID and Expansion Chassis • QXS-456 RAID and Expansion Chassis • QXS-4 Series RAID and Expansion Physical Requirements • QXS-4 Series RAID and Expansion Rackmount Chassis Weights QXS-412/424/448 RAID and Expansion Chassis Table 10 identifies physical dimensions of the QXS-412/424/448 RAID and expansion chassis.
12 Drive Front Panel Components Figure 12 provides the 2U12 drive chassis (for the RAID or expansion chassis) with the bezel removed. Figure 12 2U12 Drive Chassis (Bezel Removed) Left Ear Right Ear 1 Chassis ID LED 2 Chassis status LED: Power/Activity 3 Drive status LED: Fault 4 Chassis status LED: Unit Locator 5 Chassis status LED: Fault/Service Required...
48 Drive Front Panel Components Figure 14 provides the 2U48 drive chassis (for the RAID or expansion chassis) with the bezel removed. Figure 14 2U48 Drive Chassis (Bezel Removed) 1 Chassis ID LED 2 Thumbscrew (for securing or accessing drawers) 3 Disabled Button (used by engineering only) 4 Drawer Handle (shown in stowed position) 5 Drawer Status LED: FRU OK...
Figure 16 provides the controller I/O module (with ports identified). Controller I/O Module Figure 16 PORT 0 PORT 1 PORT 2 PORT 3 CACHE SERVICE–2 LINK SERVICE–1 DIRTY CLEAN LINK 1 CNC FC or iSCSI SFP+ Ports (used for host 2 CLI Port (USB - Type B) connection or replication) 3 Service Port 2 (Service Personnel Use Only)
Figure 18 provides the 12, 24, and 48 drive expansion I/O module (ports identified). Expansion I/O Module (ports identified) Figure 18 SERVICE LINK LINK 1 Disabled button (used by engineering/test only) 2 Service port (used by service personnel only) 3 mini-SAS In port 4 mini-SAS Out port QXS-456 RAID and Expansion Chassis Table 12...
Bezel The QXS 4U drive chassis includes a bezel sub-assembly that attaches to the front panel of the chassis. The bezel, comprised of a vented cover attached to an electro-magnetic interference (EMI) shield, is pre-assembled and packed within a box contained in the enclosure master shipping container.
56 Drive RAID Chassis: Rear Panel Components Figure 20 provides the 4U56 drive RAID chassis (rear panel components). 4U56 rear panel components Figure 20 Drive RAID Chassis ( PORT 0 PORT 1 PORT 2 PORT 3 PORT 0 PORT 1 PORT 2 PORT 3 CACHE...
56 Drive Expansion Chassis: Rear Panel Components Figure 22 provides the 4U56 drive expansion chassis (rear panel components). 4U56 rear panel components Figure 22 Drive Expansion Chassis ( SERVICE SERVICE LINK LINK LINK LINK 1 Expansion I/O module A 2 Expansion I/O module B 3 AC power supply switch 4 Power supply module 5 Fan control module (FCM)
QXS-4 Series RAID and Expansion Physical Requirements The QXS-4 series RAID and Expansion chassis consist of the following systems: • QXS-412 (12-drive, LFF drives) • QXS-424 (24-drive, SFF drives) • QXS-448 (48-drive, SFF drives) • QXS-456 (56-drive, LFF drives) The floor space at the installation site must be strong enough to support the combined weight of the rack, RAID chassis, expansion chassis, and any additional equipment.
QXS-4 Series RAID and Expansion Rackmount Chassis Dimensions Table 14 provides the RAID and expansion rackmount chassis dimensions for the 12, 24, and 48-drive chassis. Table 14 QXS-4 Series RAID and Expansion Rackmount Chassis Dimensions (12, 24, & 48-Drive Chassis) Specifications Rackmount 2U Height (y-axis):...
Chapter 4 QXS-6 Series Specifications This chapter provides the following information: • QXS-648 RAID and Expansion Chassis • QXS-656 RAID and Expansion Chassis • QXS-6 Series RAID and Expansion Physical Requirements • QXS-6 Series RAID and Expansion Rackmount Chassis Weights QXS-648 RAID and Expansion Chassis Table 18 identifies physical dimensions of the QXS-648 RAID and expansion chassis.
Bezel The QXS 2U drive chassis includes a bezel sub-assembly that attaches to the front panel of the chassis. The bezel, comprised of a vented cover attached to an electro-magnetic interference (EMI) shield, is pre-assembled and packed within a box contained in the enclosure master shipping container.
Figure 26 provides the controller I/O module (with ports identified). Controller I/O Module Figure 26 6Gb/s MGMT EXP 0 EXP 1 PORT 0 PORT 1 PORT 2 PORT 3 CACHE LINK 1 LINK S ERVICE−2 S ERVICE−1 LINK 0 = FC LEDs = 10GbE iSCSI LEDs 1 CNC FC or iSCSI SFP+ Ports (used for host 2 CLI Port (USB - Type B)
Figure 28 provides the 48 drive expansion I/O module (ports identified). Expansion I/O Module (ports identified) Figure 28 6Gb/s 6Gb/s 6Gb/s 6Gb/s S ERVICE LINK LINK LINK LINK 1 HD Mini-SAS In port 2 Service port (used by service personnel only) 3 HD Mini-SAS Out port QXS-656 RAID and Expansion Chassis Table 20...
Bezel The QXS 4U drive chassis includes a bezel sub-assembly that attaches to the front panel of the chassis. The bezel, comprised of a vented cover attached to an electro-magnetic interference (EMI) shield, is pre-assembled and packed within a box contained in the enclosure master shipping container.
QXS-6 Series RAID and Expansion Physical Requirements The QXS-6 series RAID and Expansion chassis consist of the following systems: • QXS-448 (48-drive, SFF drives) • QXS-456 (56-drive, LFF drives) The floor space at the installation site must be strong enough to support the combined weight of the rack, RAID chassis, expansion chassis, and any additional equipment.
Chapter 5 Environment and Requirements This chapter provides the following information: • Site Requirements • Weight and Placement Guidelines • Electrical Guidelines • Ventilation and Cabling Requirements • Management Host Requirements • RAID and Expansion Chassis Environmental Requirements Site Requirements The following sections provide requirements and guidelines that you must address when preparing your site for the installation.
RAID and Expansion Chassis Site Wiring and AC Power Requirements Table 26 provides the RAID chassis AC power requirements required for all installations using AC power supplies in the QXS 12, 24, 48, and 56-drive systems. Table 26 QXS RAID Chassis 12, 24, 48, and 56-Drive Power Requirements (AC Input) Measurement (AC) Rating for 12-Drive Rating for 24-Drive...
• To ensure redundancy, provide two separate power sources for the chassis . These power sources must be independent of each other, and each must be controlled by a separate circuit breaker at the power distribution point. • The system requires voltages within minimum fluctuation. The customer-supplied facilities’ voltage must maintain a voltage with not more than ±...
• To ensure redundancy, provide two separate power sources for the chassis . These power sources must be independent of each other, and each must be controlled by a separate circuit breaker at the power distribution point. • The system requires voltages within minimum fluctuation. The customer-supplied facilities’ voltage must maintain a voltage within the range specified on the equipment’s electrical rating label.
Ventilation and Cabling Requirements This section includes the following information: • Ventilation Requirements • Cabling Requirements Ventilation Requirements Ventilation requirements include: • Do not block or cover ventilation openings at the front and rear of an chassis. Never place an chassis near a radiator or heating vent.