Pos : 660 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/F ehl er E011 [SK 180E ... SK 5xxE] @ 2\mod_1347453318765_14638.doc x @ 46627 @ @ 1
E011
11.0
Control terminals,
"Customer Unit"
Pos : 661 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/F ehl er E012 [SK 180E/SK 2xxE/SK2xxE-FD S] @ 2\mod_1347454267926_14638.doc x @ 46727 @ @ 1
E012
12.0
External watchdog
12.1
Limit moto./Customer
"Motor switch-off limit"
12.2
Limit gen.
"Generator switch-off limit"
12.3
Torque limit
12.4
Current limit
12.5
Load monitor
12.8
AI minimum,
"Analog In minimum"
12.9
AI maximum,
"Analog In maximum"
Pos : 662 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265496 @ @ 1
BU 0240 en-US-3118
6 Operating status messages
Error analog – digital – inverter
Internal customer unit (internal databus) faulty or
damaged by radio radiation (EMC)
Check control connections for short circuit.
Minimize EMC interference by laying control and
power cables separately.
Device and shielding must be well grounded.
The Watchdog function is selected at a digital input and the
impulse at the corresponding digital input is not present for
longer than the time set in parameter P460 >Watchdog
time<.
Check connections
Check setting P460
The drive switch-off limit (P534 [-01]) has triggered.
Reduce load on motor
Set higher value in (P534 [-01]).
The generator switch-off limit (P534 [-02]) has triggered.
Reduce load on motor
Set higher value in (P534 [-02]).
Limit from potentiometer or setpoint source has switched off.
P400 = 12
Limit from potentiometer or setpoint source has switched off.
P400 = 14
Switch-off due to overshooting or undershooting of
permissible load torques ((P525) ... (P529)) for the time set
in (P528).
Adjust load
Change limit values ((P525) ... (P527))
Increase delay time (P528)
Change monitoring mode (P529)
Switch-off due to undershooting of the 0% adjustment value
(P402) with setting (P401) "0-10 V with switch-off on error 1"
or "....2"
Switch-off due to overshooting of the 100% adjustment
value (P402) with setting (P401) "0-10 V with switch-off on
error 1" or "....2"