NORDAC FLEX (SK 200E ... SK 235E) – Brief instructions for Frequency Inverters
The following applies as of firmware version V1.4 R2:
All parameter changes are made in the internal EEPROM. If an external EEPROM has been connected, all
changes are automatically stored on this as well. The external EEPROM therefore acts as an additional data
backup. Parameter P550 can be used to transfer data from the external EEPROM to the internal EEPROM (e.g.
during the data transfer between different devices of the same type). It is also possible to trigger the copying
procedure using DIP switches ( Section 4.2.2.2 "DIP switches (S1)").
The relevant parameters for the device are described below. Please refer to the respective
supplementary manuals for explanations for parameters which concern the field bus options or the
special functionality of the POSICON, for example.
Pos : 274 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Allgemei n/Par ameter _03 [SK 2xxE, SK 2xxE-FD S] @ 9\mod_1447403754466_14638.doc x @ 263206 @ @ 1
The individual parameters are combined in functional groups. The first digit of the parameter number
indicates the assignment to a menu group:
Menu group
Status displays
Basic parameters
Motor data
Speed control
Control terminals
Additional
parameters
Positioning
Information
Pos : 275 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Allgemei n/IN FORM ATION - Wer ks ei nstellung P523 [SK 1x0E, SK 2xxE, SK2xxE-FDS] @ 9\mod_1447404278598_14638.doc x @ 263239 @ @ 1
Information
The factory settings of the entire parameter set can be loaded at any time using parameter P523. For example,
this can be useful during commissioning if it is not known which device parameters have been changed earlier
and could have an unexpected influence on the operating behavior of the drive.
The restoration of the factory settings (P523) normally affects all parameters. This means that all motor data must
subsequently be checked or reconfigured. However, parameter P523 also provides a facility for excluding the
motor data or the parameters relating to bus communication when the factory settings are restored.
To save the current device settings, these can be transferred to a Parameter Box memory beforehand (see 
BU0040).
Pos : 276 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265496 @ @ 1
68
No.
(P0--)
Display of parameters and operating values
(P1--)
Basic device settings, e.g. behavior when switching on and off
(P2--)
Electrical settings for the motor (motor current or starting voltage)
(P3--)
Setting of current and speed controllers and settings for rotary encoders
(incremental encoders) and settings for the integrated PLC
(P4--)
Assignment of functions for the inputs and outputs
(P5--)
Mainly monitoring functions and other parameters
(P6--)
Setting of the positioning function (details  BU0210)
(P7--)
Display of operating values and status messages
Master function
Factory setting P523
BU 0240 en-US-3118