Field Setting Error - Daikin VAM 350GJVE Service Manual

Heat reclaim ventilation
Hide thumbs Also See for VAM 350GJVE:
Table of Contents

Advertisement

Si71-502
1.12

Field Setting Error

Remote Controller
Error Code
LCD Display
LED Indication
Remote Controller
Error Detection
Method
Error Generating
Conditions
Possible Causes
Troubleshooting
<Combination-Right or Wrong>
Main body
Heat reclaim ventilation unit only
Heat reclaim ventilation unit only
Heat reclaim ventilation unit + air-conditioner
Heat reclaim ventilation unit + air-conditioner
Troubleshooting
UA
Inspection Blinking Unit No. OFF
1
Main Unit
Faulty combination of remote controller
More than 16 units connected to remote controller cable.
Faulty remote controller
Is
combination
of remote
controller and heat
reclaim ventilation
unit (air
conditioner)
correct?
YES
Are
17 or more
units connected
to remote
controller
cable?
YES
5
NO
Refer "Combination-Right or Wrong"
NO
Remote controller
Heat reclaim ventilation unit
Air conditioner
Heat reclaim ventilation unit
Air-conditioner
Troubleshooting
Check the system, and correct
connections.
Change connections so that 16
or fewer units are connected to
remote controller cable.
Replace remote controller.
(HF011)
Right/Wrong
Right
Right
Wrong
Right
47