Product Specification
Model name
Power supply
Temperature exchange efficiency
Enthalpy
Cooling
exchange
efficiency
Heating
Casing
Insulation material
Dimensions
Heat exchange system
Heat exchange element
Air filter
Fan
Type
Air flow
Heat
rate
exchange
mode
External static pressure Ultra-High
Fan motor
Motor output
Operating
Heat exchange mode
sound
Bypass mode
Operation range (Ambient)
Connection duct diameter
Weight
Drawing number
Test conditions are as follows.
Note:
1. Operation sound is measured at 1.5 m below the center of the body.
2. Air flow rate can be changed over to Low mode or High mode.
3. Normal AMP., input, efficiency depend on the other above conditions.
4. Operating sound is measured in an anechoic chamber.
5. The sound level at the air discharge port is about 8 dB higher than the unit's operating sound.
6. The specifications, designs and information here are subject to change without notice.
7. Temperature Exchange Efficiency is the mean value in cooling and heating.
8. Efficiency is measured under the following conditions.
8
Ultra-High
%
High
%
Low
%
Ultra-High
%
High
%
Low
%
Ultra-High
%
High
%
Low
%
H × W × D
mm
387 × 1,111× 1,214
3
Ultra-High
m
/ h
3
High
m
/ h
3
Low
m
/ h
Pa
High
Pa
Low
Pa
Type
kW
Ultra-High
dBA
39.5 – 41.5 / 39.5
High
dBA
37.5 – 39.5 / 37.5
Low
dBA
Ultra-High
dBA
40.5 – 42.5 / 40.5
High
dBA
38.5 – 40.5 / 38.5
Low
dBA
mm
kg
Condition
Cooling condition
Heating condition
Operating sound level generally may become greater than this value depending on the operating
conditions, reflected sound, and peripheral noise.
Ratio of rated external static pressure has been kept as follows. Outdoor side to indoor side = 7 to 1
VAM1000GJVE
VAM1500GJVE
Single phase 220 – 240 V / 220 V, 50 / 60 Hz
78 / 78
78 / 78
80.5 / 81
64 / 64
64 / 64
68.5 / 69
70 / 70
70 / 70
72.5 / 73
Galvanized steel plate
Self-extinguishable urethane foam
785 × 1,619 × 832
Air to air cross flow total heat (sensible heat + latent heat) exchange
Specially processed nonflammable paper
Multidirectional fibrous fleeces
1,000 / 1,000
1,000 / 1,000
860 / 840
168 / 192
110 / 86
85 / 60
Open type capacitor permanent split-phase induction motor, 4 poles × 2
0.280 × 2
39.5 – 41.5 / 41.5
37.5 – 39.5 / 39.5
35 – 37.5 / 34.5
39.5 – 41 / 41.5
36 – 38.5 / 35.5
36.5 – 38 / 37.5
–15°C to 50°CDB (80% RH or less)
φ 250
67
C : 4D051123
Indoor
°CDB
R·H (%)
27
50
20
40
VAM2000GJVE
72 / 72
72 / 72
75.5 / 76
61 / 61
61 / 61
64 / 64.5
65 / 65
65 / 65
67 / 67.5
785 × 1,619 × 1,214
Sirroco fan
1,500 / 1,500
2,000 / 2,000
1,500 / 1,500
2,000 / 2,000
1,320 / 1,260
1,720 / 1,580
112 / 150
73 / 72
56 / 50
0.280 × 4
41.5 – 43.5 / 42
35 – 37.5 / 36
41 – 43 / 42.5
43 – 45.5 / 44
40.5 – 45 / 42
37.5 – 39.5 / 41
φ 350
129
C : 4D051119
C : 4D051124
Outdoor
°CDB
35
7
Product Specification
Si71-502
(50 / 60Hz)
77 / 77
77 / 77
79 / 81
62 / 62
62 / 62
66 / 67
72 / 72
72 / 72
75 / 76
116 / 140
58 / 32
45 / 45
0.280 × 4
39 – 43 / 40
36 – 39 / 39
φ 350
157
R·H (%)
60
70