Commissioning and configuration

12
Commissioning and configuration
12.1

Measures to be performed prior to the initial commissioning

 Before commissioning, familiarize yourself with the operation and configuration of the
MA 208i.
 Before connecting the supply voltage, recheck all connections and ensure that they
have been properly made.
The Leuze device must be connected to the internal RS 232 device interface.
Connecting the Leuze device
 Open the housing of the MA
for BCL 32) through the middle threaded opening.
 Connect the cable to the internal device interface (X30, X31 or X32, see chapter 7.5.1).
 Use rotary switch S4 (see chapter 8.2.5) to select the connected device.
 Now screw the PG cable gland into the threaded opening to provide strain relief and
ensure protection class IP 65.
 Finally, close the housing of the MA 208i.
Attention!
Only then may the supply voltage be applied.
Upon startup of the MA 208i, the device selection switch is queried and the gateway
automatically sets itself to the Leuze device.
PWR IN
SWIO_2
2
GND
3
1
5
4
FE
SWIO_1
M 12 connector
(A-coded)
Figure 12.1: Connections of the MA 208 seen from below, device on mounting plate
 Check the applied voltage. It must be in the range between +18V ... 30 V DC.
Connecting functional earth FE
 Ensure that the functional earth (FE) is connected correctly.
Unimpaired operation is only guaranteed when the functional earth is connected properly.
All electrical disturbances (EMC couplings) are discharged via the functional earth connec-
tion.
On delivery, the SWIO 1/2 are connected in parallel on PWR IN/OUT. This connection can
be separated with a jumper.
52
208i
PWR OUT
SWIO_2
2
VIN
VOUT 1
3
5
4
FE
SWIO_1
M 12 socket
(A-coded)
and guide the corresponding device cable (e.g., KB 031
LEUZE Device
GND
MA
208i
HOST / BUS IN
RD+
2
TD+ 1
TD-
3
4
RD-
M 12 socket
(D-coded)
Leuze electronic
BUS OUT
RD+
2
TD+ 1
TD-
3
4
RD-
M 12 socket
(D-coded)