Telegram; Structure Of The Fieldbus Telegram - Leuze electronic MA 208i Technical Description

Modular interfacing unit for leuze ident and rs 232 devices on ethernet tcp/ip
Table of Contents

Advertisement

Telegram

10
Telegram
10.1

Structure of the fieldbus telegram

All operations are performed by control and status bits. Two bytes of control information
and two bytes of status information are available for this purpose. The control bits are a part
of the output module and the status bits are a part of the input bytes. The data starts with
the third byte.
If the actual data length is longer than the data length configured in the gateway, only part
of the data is transmitted; the remaining data is lost. In this case, the DL (data loss) bit is set.
The following telegram structure is used between PLC -> fieldbus gateway:
7
ND
Address 4
This telegram structure is used between fieldbus gateway -> PLC:
7
ND
Reserved
DLC7
Only the data part with the corresponding frame (e.g., STX, CR & LF) is then transmitted
between the fieldbus gateway and the Leuze end device. The two control bytes are
processed by the fieldbus gateway.
The corresponding control and status bits and their meaning are specified in section 10.2
and section 10.3.
Further information on the broadcast control bytes and address bits 0 ... 4 can be found in
chapter "Modular interfacing unit MA 3x (S4 switch position C)" on page 81.
44
6
5
Address 3
Address 2
Data byte / parameter byte 0
Data byte / parameter byte 1
6
5
4
DL
Reserved Reserved
DLC6
DLC5
DLC4
Data byte / parameter byte 0
Data byte / parameter byte 1
4
3
2
Address 1
Address 0
Reserved
Reserved
...
3
2
SMA
DLC3
DLC2
...
MA
208i
1
0
Broadcast Command
mode
Reserved
1
0
Reserved
DLC1
DLC0
Leuze electronic
Control byte 0
Control byte 1
Data
Status byte 0
Status byte 1
Data