Ma 208 On Ethernet; Manually Setting The Ip Address - Leuze electronic MA 208i Technical Description

Modular interfacing unit for leuze ident and rs 232 devices on ethernet tcp/ip
Table of Contents

Advertisement

Fast commissioning / operating principle
3.5
MA
208i
Setting the communication parameters
With the communication parameters, you determine how data is exchanged between
MA
208i
and host system, monitor PCs etc.
The communication parameters are independent of the topology in which the MA
operated (see "Ethernet" on page 18).
On delivery from firmware 1.1.0.0, automatic address assignment is deactivated via DHCP
and a permanent IP address is set:
Device address:
Net mask:
The setting can be adapted via Leuze configuration software BCL-Config, BPS-Config or
RF-Config. In these tools, the MA
parameters in the usual way via the service interface.
3.5.1

Manually setting the IP address

If the IP address of the devices should be permanently set on your system, proceed as
follows:
 Have the network administrator specify the data for IP address, net mask and gateway
address of the MA 208i.
 Select the connected device via the device selection switch.
 Apply the supply voltage +18 ... 30 V DC (typ. +24 V DC); the MA
 Now switch the service switch to "MA".
Notice!
The service switch must be in switch position "MA" here so that the MA
addressed via the service interface.
 Connect the serial RS 232 Sub-D interface of the MA
PC.
 Make the necessary settings in the configuration window.
12
on Ethernet
192.168.61.100.
255.255.255.0
208i
has been created as a device to enable setting of
MA
208i
208i
starts up.
208i
to the serial interface of your
Leuze electronic
208i
is
208i
can be