Connecting Heating Circuits With Permeable Pipework - Viessmann Sub Mounting Kit Installation Instructions Manual

Heating circuit distributor for vitodens 200-w up to 35 kw
Table of Contents

Advertisement

Connecting the heating circuits
System scheme with sub-mounting kit
A
Fig. 8
Heating circuit without mixer
A
Heating circuit with mixer (underfloor heating cir-
B
cuit)
Bypass
C
Volume balancing line
D
Plate heat exchanger for system separation
E
3-way mixer
F
Heating circuit pump
G
Flow temperature sensor
H
Temperature limiter to restrict the maximum tem-
K
perature of underfloor heating systems

Connecting heating circuits with permeable pipework

When connecting heating systems with permeable
pipework (DIN 4726), seal off the volume balancing
line between the two heating circuits.
Removing the volume balancing line
1.
Fig. 9
10
(cont.)
B
K
H
C
G
F
M
E
D
2.
Information regarding the heating circuit with
mixer
Install a drain & fill valve on site, in the flow of the heat-
ing circuit with mixer. This is required during commis-
sioning for filling and venting the heating circuit.
The expansion vessel integrated into the boiler can
also be used for the heating circuit with mixer.
Check whether the size of the integral expansion ves-
sel is adequate for the connected heating circuits.
Information on the underfloor heating circuit
Fit maximum temperature limiter
line at least 1 m downstream of the circulation pump.
Note
If the volume balancing line has been removed, install
a separate expansion vessel in the regulated heating
circuit.
1. Undo the union nuts and remove the balancing line
and locking rings.
2. Seal the connections with the plugs and union nuts
supplied.
Lubricate the O-rings with the valve grease sup-
plied.
to the heating flow