Profinet-Io Wiring; Cable Lengths And Shielding - Leuze electronic MA 248i Original Operating Instructions

Feldbus gateway – profinet-io
Table of Contents

Advertisement

Electrical connection
7.6

PROFINET-IO wiring

A Cat. 5 Ethernet cable should be used for wiring.
For the connection technology transition from M12 to RJ45, a "KDS ET M12/RJ 45 W - 4P"
adapter is available that lets you connect standard network cables.
If no standard network cables are to be used (e.g., due to lacking IP... protection class),
you can use the "KB ET - ... - SA" user-configurable cables on the side of the MA 248i, see
table 14.4 Bus connection cable for the MA 248i on page 84.
The individual MA
"KB ET - ... - SSA" cable, see "Bus connection cable for the MA 248i" on page 84.
For unavailable cable lengths, you can configure your cables yourself. When doing so, make
certain that you connect TD+ on the M12 connector with RD+ on the RJ-45 connector and
TD- on the M12 connector with RD- on the RJ-45 connector, respectively, etc.
Notice!
Use the recommended connectors / sockets or the ready-made cables (see chapter 14 "Type
overview and accessories").
For further information on the topologies, see chapter 4.5.1 "PROFINET-IO".
7.7

Cable lengths and shielding

 Observe the following maximum cable lengths and shielding types:
Connection
MA 248 – – Service
MA 248 – Host
MA 248 – Power
supply unit
Switching input
Switching output
Table 7.5:
38
248i
devices in a linear topology are connected with the
Interface
RS 232
PROFINET-IO RT
Cable lengths and shielding
MA
Max. cable length
10m
100m
30m
10m
10m
248i
Shielding
not necessary
absolutely required, shielded
not necessary
not necessary
not necessary