This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes.
Topic
Updated template
Removed discontinued Catalog Number 1794-IJ2K
Updated Environment and Enclosure
Updated European and IEC Hazardous Location Approvals
Installation Instructions Original Instructions FLEX I/O 2-input Frequency Modules Catalog Numbers 1794-IJ2, 1794-IJ2XT Topic Page Summary of Changes Environment and Enclosure Prevent Electrostatic Discharge European Hazardous Location Approval North American Hazardous Location Approval Install Your Frequency Input Module Connecting Wiring for the 1794-TB3G and 1794-TB3GS Terminal Base Unit Resolution and Accuracy Interpret Status Indicators Diagnostics...
Page 2
Indien de apparatuur wordt gebruikt op een wijze die niet is gespecificeerd door de fabrikant, dan bestaat het gevaar dat de beveiliging van de apparatuur niet goed werkt. Rockwell Automation Publication 1794-IN049E-EN-P - May 2022...
Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately. Be sure to ground the DIN rail properly. See the Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for more information.
• This equipment shall be used within its specified ratings defined by Rockwell Automation. • Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the peak rated voltage when applied in Zone 2 environments.
ATTENTION: To reduce susceptibility to noise, power analog modules and digital modules from separate power supplies. Do not exceed a length of 3 m (9.8 ft) for DC power cabling. ATTENTION: Do not daisy chain power or ground from this terminal base unit to any AC or DC digital module terminal base units. Rockwell Automation Publication 1794-IN049E-EN-P - May 2022...
Page 6
(5) Add external resistor from 24V to F (A-6) or G (A-9) for wire-off detection (0.4 mA). (6) Add jumper between 50 mV and RET (frequency - channel 0 = A-4…A-3; channel 1 = A-11…A-12) Rockwell Automation Publication 1794-IN049E-EN-P - May 2022...
The indicator turns red in about 1.5 s if there is an internal diagnostics error. The module is operating correctly when the green OK indicator is on. A red OK indicator shows that the module is in a Faulted condition (internal error). Rockwell Automation Publication 1794-IN049E-EN-P - May 2022...
32,767 Hz or 3,276.7 Hz (overange). The % Full Scale calculation (based on Max Frequency) is > 3,276.7%. 1010...1111 10...15 = Not used Diagnostic Status - indicates the response from the module; a normal or non-normal operating condition. Rockwell Automation Publication 1794-IN049E-EN-P - May 2022...
Outputs individually assignable to: Frequency, % Full Scale, or Acceleration Alarm Triggered by frequency alarm or acceleration alarm Output switching time Turn on: Less than 0.5 ms Turn off: Less than 1 ms Rockwell Automation Publication 1794-IN049E-EN-P - May 2022...
Page 12
GB 3836.1-2010 Explosive atmospheres — Part 1: Equipment — General requirements GB 3836.8-2014 Explosive atmospheres - Part 8: Equipment protection by type of protection “n” (1) See the Product Certification link at rok.auto/certifications for Declarations of Conformity, Certificates, and other certification details. Rockwell Automation Publication 1794-IN049E-EN-P - May 2022...
Page 13
FLEX I/O 2-input Frequency Modules Installation Instructions Notes: Rockwell Automation Publication 1794-IN049E-EN-P - May 2022...
Page 14
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur Connect with us. Allen-Bradley, expanding human possibility, FactoryTalk, FLEX, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.