Siemens SITRANS F Series Operating Instructions Manual page 199

Coriolis flowmeters
Hide thumbs Also See for SITRANS F Series:
Table of Contents

Advertisement

Modbus ad‐
Data type /
dress
Size (bytes)
4131
String / 32
4147
String / 32
4164
String / 32
4180
String / 16
4188
String / 16
Table B-4
Operating conditions
Modbus ad‐
Data type /
dress
Size [bytes]
2100
Unsigned /
2
2130
Unsigned /
2
FC310 (From firmware 4.0)
Operating Instructions, 06/2018, A5E44036384-AA
Parameter
Description
Sensor Order Num‐
Sensor order number part 2
ber
(MLFB).
Also shown on the device
nameplate
Sensor Order Num‐
Sensor order number part 3
ber
(MLFB).
Also shown on the device
nameplate
Long TAG
Enter a unique TAG name
for the device (up to 32 char‐
acters)
Descriptor
Enter a unique description
for the measurement point
(up to 16 characters)
Startup Date
Enter the installation date of
the device
Parameter
Description
Flow Direction
Define positive and negative
flow direction.
Default positive flow direc‐
tion is indicated by the arrow
on the sensor.
Possible selections:
● 0: Negative: The flow is
● 1: Positive: The flow is
Process Noise
Select process noise damp‐
Damping
ing level:
0: 55 ms filtering (Centrifugal
Pump)
1: 110 ms filtering (Triplex
Pump)
2: 220 ms filtering (Duplex
Pump)
3: 400 ms filtering (Simplex
Pump)
4: 800 ms filtering (Cam
Pump)
measured '+' in default
negative direction and '-'
in default positive
direction.
measured '+' in default
positive direction and '-'
in default negative
direction
Modbus communication
B.3 Modbus holding registers tables
Default value
Value range Access
(unit)
-
-
-
-
Default value
Value range Access
[unit]
1
0 to 1
2
0 Low to 4
High
level
Read Only
Read Only
level
Read /
Write
Read /
Write
199