Diagnostics and troubleshooting
10.3 Sensor diagnostic events
ID/
Diagnostic
Icons
69
Empty Tube Limit' exceeded
70
Too little fluid in tube
71
Parameter storage malfunction
72
Internal error in sensor
73
Internal error in sensor
74
Internal error in sensor
75
Internal error in sensor
76
Internal error in sensor
77
Internal error in sensor
122
Action
Make sure that the sensor is filled with liquid and
that the liquid density is within the specified
'Empty Tube Limit'
Make sure that the sensor is filled with liquid
Turn off the power, wait 5 seconds and turn on
the power again. If the failure continues then
contact your local Siemens representative
Contact your local Siemens representative
Contact your local Siemens representative
Contact your local Siemens representative
Contact your local Siemens representative
Contact your local Siemens representative
Contact your local Siemens representative