Electrical Connections; Analog Indicator With Alarm Signaling Unit - ABB VA Master FAM540 Commissioning Instructions

Metal cone variable area flowmeter
Hide thumbs Also See for VA Master FAM540:
Table of Contents

Advertisement

Model FAM544 - Hygienic design
Process
Nominal
connection
Diameter
DIN 11851
DN 15 ... 40
(1/2 ... 1 1/2")
DN 50 ... 100
(2 ... 4")
DN 125 (5")
SMS 1145
DN 38 ... 102
(1 1/2 ... 4")
Model FAM545 - With PTFE liner and Model FAM546 -
With heating jacket
Fig. 17: DIN flange made from stainless steel
Fig. 18: ASME flange made from stainless steel
PS
TS
TS
max
min
max
40 bar
-40 °C
140 °C
(580 psi)
(-40 °F)
(284 °F)
25 bar
-40 °C
140 °C
(362 psi)
(-40 °F)
(284 °F)
16 bar
-40 °C
140 °C
(232 psi)
(-40 °F)
(284 °F)
6 bar
-40 °C
140 °C
(87 psi)
(-40 °F)
(284 °F)
6.5

Electrical connections

DANGER
Improper installation and commissioning of the device
carries a risk of explosion.
For use in potentially explosive atmospheres, observe the
information in chapter „Use in potentially explosive
atmospheres according to ATEX and IECEx" on page 5 and
„Use in potentially explosive atmospheres in accordance with
FM and cCSAus" on page 16!
The electrical connection may only be established by
authorized specialist personnel and in accordance with the
connection diagrams.
The electrical connection information in the manual must be
observed; otherwise, the type of electrical protection may be
adversely affected.
Ground the measurement system according to requirements.
6.5.1

Analog indicator with alarm signaling unit

Model FAM54xB/C/Dx
Fig. 19: Alarm signaling unit
1 Maximum alarm signaling unit 2 Minimum alarm signaling unit
3 Switch amplifier F Flowmeter
Additional switching amplifiers are needed to operate the
alarm signaling units.
See chapter „Switching amplifier" on page 32 and the
"Ordering information" section of the data sheet for further
information.
Alarm signaling unit specifications
Operating mode
Reproducibility
Nominal voltage
Operating voltage
Switching frequency, max.
VA Master FAM540 | CI/FAM540-EN Rev. B 31
bistable
±0.5% of scale end value
8 V DC (Ri approx. 1 kΩ)
5 ... 25 V DC
3 kHz

Advertisement