Note for discharge-side installation: To protect the piping, use
a pulsation damper (8i) for rigid piping longer than 3 metres
and tubing longer than 5 metres.
Installation with discharge-side pulsation damper
Fig. 8
For degassing and viscous media: flooded suction.
To protect the dosing pump and the discharge line against
excessive pressure build-up, install a relief valve (6i) in the
discharge line.
Installation with relief valve
Fig. 9
With open outflow of the dosing medium or a counter-
pressure below 1 bar
Install a pressure-loading valve (7i) immediately before the
outlet or the injection unit.
A positive pressure difference of at least 1 bar must be ensured
between the counter-pressure at the injection point and the
pressure of the dosing medium at the pump suction valve.
If this cannot be ensured, install a pressure-loading valve (7i)
in the discharge line.
7i
Fig. 10 Installation with pressure-loading valve
8i
p
6i
10i
p ≥ 1 bar
p
1 bar
To avoid the siphon effect, install a pressure-loading valve (7i)
in the discharge line and, if necessary, a solenoid valve (14i) in
the suction line.
Fig. 11 Installation to avoid the siphon effect
Warning
Risk of hot surfaces!
Pumps with AC motors may become hot.
Allow a minimum space of 100 mm to the fan
cover!

8.3 Mounting

Mount the pump horizontally on the tank or on a console using
four M8 screws.
Gently tighten the screws in order not to damage
Caution
the plastic enclosure!

8.4 Tube / pipe lines

8.4.1 General
Warning
To protect the dosing pump against excessive
pressure build-up, install a relief valve in the
discharge line.
Only use the prescribed line types!
All lines must be free from strain!
Avoid loops and buckles in the tubes!
Keep the suction line as short as possible to
avoid cavitation!
If necessary, use swept bends instead of elbows.
Observe the chemical manufacturer's safety
instructions when handling chemicals!
Make sure that the pump is suitable for the actual
dosing medium!
The flow must run in the opposite direction to
gravity!
The resistance of the parts that come into contact
with the media depends on the media, media
temperature and operating pressure. Ensure that
Caution
parts in contact with the media are chemically
resistant to the dosing medium under operating
conditions!

8.5 Connecting the suction and discharge lines

Warning
All lines must be free from strain!
Only use the prescribed line types!
Connect the suction line to the suction valve.
– Install the suction line in the tank so that the foot valve
remains 5 to 10 mm above the bottom of the tank or the
possible level of sedimentation.
Connect the discharge line to the discharge valve.
p
-p
≥ 1 bar
p
>
p - p
1 bar
2
1
_
1
2
1
p
2
14i