Time Delayed Derived Earth Fault Protection (51N) - Siemens 7SR10 Argus Series Manual

Overcurrent relay
Table of Contents

Advertisement

3.2.3

Time Delayed Derived Earth Fault Protection (51N)

Two time delayed derived earth fault elements are provided in the 7SR1002/7SR1003 relay and four elements are
provided in the 7SR1004 relay.
51N-n Setting sets the pick-up current level.
A number of shaped characteristics are provided. An inverse definite minimum time (IDMT) characteristic is
selected from IEC and ANSI curves using 51N-n Char. A time multiplier is applied to the characteristic curves
using the 51N-n Time Mult setting. Alternatively, a definite time lag delay (DTL) can be chosen using 51N-n
Char. When definite time lag (DTL) is selected the time multiplier is not applied and the 51N-n Delay (DTL)
setting is used instead.
The 51N-n Reset setting can apply a definite time delayed reset, or when the operation is configured as an IEC
or ANSI or user characteristic if the reset is selected as IEC/ANSI (DECAYING) reset the associated reset curve
will be used. The reset mode is significant where the characteristic has reset before issuing a trip output – see
'Applications Guide'
A minimum operate time for the characteristic can be set using the 51N-n Min. Operate Time setting.
A fixed additional operate time can be added to the characteristic using the 51N-n Follower DTL setting.
Where directional elements are present the direction of operation can be set using 51N-n Dir. Control setting.
Directional logic is provided independently for each 51N-n element e.g. giving the option of using two elements
set to forward and two to reverse.
Operation of the time delayed earth fault elements can be inhibited from:
Inhibit 51N-n
79 E/F Inst Trips: 51N-n
51N-n Inrush Action: Block
51N-n VTSAction: Inhibit
©2018 Siemens Protection Devices Limited
51N-1, 51N-2, (51N-3 & 51N-4 – 7SR1004)
A binary or virtual input.
When 'delayed' trips only are allowed in the auto-reclose sequence
(79 E/F Prot'n Trip n = Delayed).
Operation of the inrush current detector function.
Operation of the VT Supervision function.
7SR10 Description of Operation
Chapter 1 Page 32 of 77

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7sr1003 argus7sr1002 argus7sr1004 argus

Table of Contents