Siemens 7SR10 Argus Series Manual page 214

Overcurrent relay
Table of Contents

Advertisement

7SR10 Technical Manual
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
Point
Description
Index
108 I Phase A Max
109 I Phase B Max
110 I Phase C Max
111 P 3P Max
112 Q 3P Max
115 Isef Primary
116 Isef Secondary
117 Isef Nominal
135 CB Total Trip Count
136 CB Delta Trip Count
137 CB Count To AR Block
138 CB Frequent Ops Count
165 Ia Last Trip
166 Ib Last Trip
167 Ic Last Trip
168 Va Last Trip
169 Vb Last Trip
170 Vc Last Trip
171 In Last Trip
172 Ig Last Trip
173 Isef Last Trip
174 V Phase A Max
175 V Phase B Max
176 V Phase C Max
177 V Phase AB Max
178 V Phase BC Max
179 V Phase CA Max
184 CB Wear A
185 CB Wear B
186 CB Wear C
187 CB Wear A Remaining
188 CB Wear B Remaining
189 CB Wear C Remaining
190 CB Wear Minimum
Chapter 4 - Page 64 of 78
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
Default
Default
Change Event
Variation
Variation
Assigned Class
Static
(1, 2, 3 or none)
Object 30
Object 32
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
1
0,3
1
0,3
1
0,3
1
0,3
1
0,3
1
0,3
1
0,3
1
0,3
1
0,3
1
0,3
1
0,3
1
0,3
1
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
1
0,3
1
0,3
1
0,3
1
0,3
1
0,3
1
0,3
1
Default
Default
Event
Multiplier
4
1.000
4
1.000
4
1.000
4
10.000
4
10.000
4
1.000
4
1000.000
4
1000.000
3
1.000
3
1.000
3
1.000
3
1.000
3
1.000
3
1.000
3
1.000
3
1.000
3
1.000
3
1.000
3
1.000
3
1.000
3
1.000
4
0.010
4
0.010
4
0.010
4
0.010
4
0.010
4
0.010
3
100.000
3
100.000
3
100.000
3
1.000
3
1.000
3
1.000
3
1.000
© 2018 Siemens Protection Devices
Default
Deadband
100.000
100.000
100.000
1000000.000
1000000.000
10.000
0.050
0.050
1.000
1.000
1.000
1.000
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
100.000
100.000
100.000
100.000
100.000
100.000
1000000.000
1000000.000
1000000.000
1.000
1.000
1.000
1.000

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7sr1003 argus7sr1002 argus7sr1004 argus

Table of Contents