Sensitive Power; Reference; Operate And Reset Level; Operate And Reset Time - Siemens 7SR10 Argus Series Manual

Overcurrent relay
Table of Contents

Advertisement

2.3
32S Sensitive Power
2.3.1

Reference

Parameter
S
32S-n Setting
s
t
32S-n Delay setting
d
2.3.2

Operate and Reset Level

Attribute
S
Operate level
op
Reset level
Variation
2.3.3

Operate and Reset Time

Attribute
Element basic
t
basic
operate time
t
Operate time following delay
op
Disengaging time
2.3.4

Operate Threshold

Attribute
Minimum levels for
operation
© 2018 Siemens Protection Devices Limited
Over-power
Under-power
-10 °C to +60 °C
f
± 5 %
nom
Over-power
Under-power
I
V
Value
0.005...2xSn
0.00 ... 14400 s
Value
100 % Ss, ± 5 % or ± 2 % Sn
≥ 95 % S
op
≤ 105 % S
op
≤ 5 %
≤ 5 %
Value
1.1 x Ss: 60 ms ± 10 ms
2.0 x Ss: 45 ms ± 10 ms
0.5 x Ss: 30 ms ± 10 ms
t
+ t
, ± 1 % or ± 10 ms
basic
d
< 40 ms
Value
2.5 % I
n
2.5 % V
n