Wolf CRL Series Installation And Maintenance Instructions Manual

Wolf CRL Series Installation And Maintenance Instructions Manual

Comfort ventilation unit with thermal wheel heat exchanger

Advertisement

GB
Installation and maintenance instructions
COMFORT VENTILATION UNIT WITH THERMAL WHEEL HEAT
EXCHANGER
CRL / CRL evo max
(Translation of the original)
English | subject to modifications!
3064361_201811

Advertisement

Table of Contents
loading

Summary of Contents for Wolf CRL Series

  • Page 1 Installation and maintenance instructions COMFORT VENTILATION UNIT WITH THERMAL WHEEL HEAT EXCHANGER CRL / CRL evo max (Translation of the original) English | subject to modifications! 3064361_201811...
  • Page 2: Table Of Contents

    Table of contents Table of contents General / Safety information ..............3 Standards, regulations / disposal ............5 CRL-iD unit layout .................. 6 CRL-iD appliance versions ..............8 CRL-iH unit layout .................. 9 5.1 CRL-iH evo max unit layout ..............11 CRL-iH appliance versions ..............
  • Page 3: General / Safety Information

    1 General / Safety information General information These installation and maintenance instructions only apply to WOLF CRL / CRL evo max ventilation units. Authorised personnel should read these instructions before any commissioning or maintenance work. Comply with the specifications in this document. Installation, commissioning and maintenance work must only be carried out by trained personnel.
  • Page 4 Intended use Wolf CRL / CRL evo max ventilation units are designed to heat and filter normal air. Max. Max. air intake temperature: +40 °C. The use of these units in wet rooms or rooms with explosive atmospheres is not permissible. Handling very dusty or aggressive media is not permissible.
  • Page 5: Standards, Regulations / Disposal

    2 Standards, regulations / disposal Standards and regulations - Machinery Directive 2006/42/EC - Low Voltage Directive 2014/35/EU - EMC Directive 2014/30/EU - ErP Directive 2009/125/EC - EN ISO 12100 Safety of machinery; general principles for design - DIN EN ISO 13857: Safety of machinery;...
  • Page 6: Crl-Id Unit Layout

    3 CRL-iD unit layout CRL-iD Comfort thermal wheel heat exchanger ventilation unit for internal installation with vertical/ horizontal duct connection (example provided is CRL-iD-3500 with boost damper) Outdoor air damper with servomotor Differential pressure switch for filter monitoring Filter pre-dryer (accessory) Electric reheating coil available for CRL-1300/-2500/-3500 (accessory) Differential pressure switch for filter monitoring...
  • Page 7 3 CRL-iD unit layout Total TWHE with boost damper 1 Outdoor air 3 Supply air 2 Exhaust air 4 Extract air Type CRL-iD-1300 CRL-iD-2500 CRL-iD-3500 Unit layout Single piece Single piece Three piece Length L 1525 / 1525* 1626 / 1626* 1626 / 1830* Length L1 Length L2 (rotor part)
  • Page 8: Crl-Id Appliance Versions

    4 CRL-iD appliance versions Access side in supply air direction, left Access side in supply air direction, right For CRL-1300/-2500/-3500, these versions are available with a boost damper. 3064361_201811...
  • Page 9: Crl-Ih Unit Layout

    5 CRL-iH unit layout CRL-iH Comfort thermal wheel heat exchanger ventilation unit for internal installation with horizontal duct connection (example provided is CRL-iH-3500 with boost damper) Outdoor air damper with servomotor Differential pressure switch for filter monitoring Filter pre-dryer (accessory) Electric reheating coil available for CRL-1300/-2500/-3500 (accessory) Differential pressure switch for filter monitoring...
  • Page 10 5 CRL-iH unit layout Total TWHE with boost damper 1 Outdoor air 3 Supply air 2 Exhaust air 4 Extract air Type CRL-iH-1300 CRL-iH-2500 CRL-iH-3500 Unit layout Single piece Single piece Three piece Length L 1525 / 1525* 1626 / 1626* 1626 / 1830* Length L1 Length L2 (rotor part)
  • Page 11: Crl-Ih Evo Max Unit Layout

    5.1 CRL-iH evo max unit layout CRL-iH evo max Comfort thermal wheel heat exchanger ventilation unit for internal installation with horizontal duct connection (example provided is CRL-iH-11000 evo max with boost damper) Outdoor air damper with servomotor Extract air filter Differential pressure switch for filter monitoring BMK programming unit Ventilation air damper with servomotor...
  • Page 12 5 CRL-iH evo max unit layout Total 1 Outdoor air 3 Supply air 2 Exhaust air 4 Extract air Type CRL-iH-11000 evo max CRL-iH-13500 evo max Unit layout Five piece Five piece Length L 2950 / 2950* 2950 / 2950* Length L1 1424 1424...
  • Page 13: Crl-Ih Appliance Versions

    6 CRL-iH appliance versions Access side in supply air direction, left Access side in supply air direction, right 1, 2 1, 2 1, 2 1, 2 For CRL-iH-1300/-2500/-3500, these versions are available with a boost damper CRL-IH evo max types are available in these versions 3064361_201811...
  • Page 14: Crl-Idh Unit Layout

    7 CRL-iDH unit layout CRL-iDH Comfort thermal wheel heat exchanger ventilation unit energy efficient and comfortable ventilation with vertical/horizontal duct connection (example provided is CRL-iDH-3500 with boost damper) Outdoor air damper with servomotor Compact filter, extract air Filter pre-dryer (accessory) Differential pressure switch for filter monitoring Differential pressure switch for filter monitoring Electric reheating coil available for...
  • Page 15 7 CRL-iDH unit layout Total TWHE with boost 1 Outdoor air 3 Supply air damper 2 Exhaust air 4 Extract air Type CRL-iDH-1300 CRL-iDH-2500 CRL-iDH-3500 Unit layout Single piece Single piece Three piece Length L 1525 / 1525* 1626 / 1626* 1626 / 1830* Length L1 Length L2 (rotor part)
  • Page 16: Crl-Idh Appliance Versions

    8 CRL-iDH appliance versions Access side in supply air direction, left Access side in supply air direction, right Other versions available; see the WOLF sizing program. For CRL-1300/-2500/-3500, these versions are available with a rapid heat-up damper. 3064361_201811...
  • Page 17: Crl-A Unit Layout

    9 CRL-A unit layout CRL-A Comfort thermal wheel heat exchanger ventilation unit for external installation (weather-resistant) with horizontal duct connection (example provided is CRL-A-3500 with boost damper) Outdoor air damper with servomotor 11 Electric reheating coil available for CRL-1300/-2500/-3500 (accessory) Filter pre-dryer (accessory) 12 EC fan, supply air Differential pressure switch for filter monitoring...
  • Page 18 9 CRL-A unit layout 1 Outdoor air 2 Exhaust air 3 Supply air 4 Extract air Total Type CRL-A-1300 CRL-A-2500 CRL-A-3500 Unit layout Single piece Single piece Three piece Length L 1525 / 1525* 1626 / 1626* 1626 / 1830* Length L1 Length L2 (rotor part) 610 / 814*...
  • Page 19: Crl-A Evo Max Unit Layout

    9.1 CRL-A evo max unit layout CRL-A evo max Comfort thermal wheel heat exchanger ventilation unit for external installation (weather-resistant) with horizontal duct connection (example provided is CRL-A-11000 with boost damper) Condensate pan 11 Differential pressure switch for filter monitoring Intake hood with mist eliminator 12 control panel Outdoor air damper with servomotor...
  • Page 20 9 CRL-A evo max unit layout Total 1 Outdoor air 3 Supply air 2 Exhaust air 4 Extract air Type CRL-A-11000 evo max CRL-A-13500 evo max Unit layout Five piece Five piece Length L 2950 / 2950* 2950 / 2950* Length L1 1424 1424...
  • Page 21: Crl-A Appliance Versions

    10 CRL-A appliance versions Access side in supply air direction, left Access side in supply air direction, right ABL/ FOL/ ABL/ FOL/ ZUL/ AUL/ ZUL/ AUL/ FOL/ ABL/ FOL/ ABL/ 1, 2 1, 2 ZUL/ AUL/ ZUL/ AUL/ AUL/ AUL/ ZUL/ ZUL/ ABL/...
  • Page 22: Delivery / Handling

    If there is any damage or even a suspicion of damage, the recipient must indicate this on the consignment note and have it countersigned by the haulier. The recipient of the goods must notify WOLF of the relevant facts without delay.
  • Page 23 11 Delivery/Handling Transport external units Transport ropes with a minimum length equivalent to the eye bolt distance L must be used when transporting external CRL units with eye bolts. The same applies to the individual transport units of the CRL evo max units. External CRL evo max units may only be lifted as an entire unit with a lifting beam when pulling equally and vertically on all available eye bolts.
  • Page 24: Unit Splitting For Handling Purposes - Crl

    12 Unit splitting for handling purposes - CRL Disassembly of internal units Undo the unit connector bolts with an SW13 spanner to dismantle the unit. CRL-3500/-4800/-6200/-9000 Remove filters before dismantling in order to reach the rear unit connectors. It may be necessary to remove the dampers in order to gain better access to the rear unit connectors in this area.
  • Page 25 12 Unit splitting for handling purposes - CRL 3064361_201811...
  • Page 26 12 Unit splitting for handling purposes - CRL 3064361_201811...
  • Page 27 12 Unit splitting for handling purposes - CRL 3064361_201811...
  • Page 28 12 Unit splitting for handling purposes - CRL 3064361_201811...
  • Page 29: Assembly - Crl Evo Max

    13 Assembly - CRL evo max 3064361_201811...
  • Page 30 13 Assembly - CRL evo max 3064361_201811...
  • Page 31 13 Assembly - CRL evo max 3064361_201811...
  • Page 32: Installation Information For External Units

    Insulation against structure- borne noise The WOLF base frame and its integration into the roof membrane must be insulated onsite. In the case of elevated positioning (CRL on onsite framework), the CRL must be secured against wind load. Insulation against...
  • Page 33: Siting

    15 Siting Minimum clearance between outdoor air intake and exhaust air aperture to prevent an "air short circuit" (DIN 13779) Exhaust Supply air Outdoor Extract Outdoor Exhaust Exhaust Extract Extract Outdoor Supply Supply Functional illustration of air inflow: CRL-iD Supply air Extract air Exhaust air Outdoor air...
  • Page 34 15 Siting Installation location CRL The installation location must be level and have adequate load bearing Indoor unit capacity (see data sheets for individual unit weights). Level the unit horizontally (align using the adjustable feet). The installation site must be able to bear the load of the ventilation unit without vibrations on a long term basis.
  • Page 35: Electrical Connection

    There is no personal safety protection if the unit is operated with RCDs. Regularly check the perfect function of all electrical equipment. Observe the specified electrical fuse/MCB protection ratings. Any damage or loss resulting from technical modifications to WOLF control units is excluded from our warranty. 3064361_201811...
  • Page 36 16 Electrical connection max. Current max. Fan power IP rating / Size Rated voltage consumption Fan speed consumption protection class fans 1 x 230V CRL-1300 1.0kW 4.6A 3080 rpm IP55 / Iso F (50/60Hz) 3 x 400V CRL-2500 2.1kW 3.2A 3400 rpm IP55 / Iso F (50/60Hz)
  • Page 37: Commissioning

    1000 V DIN VDE 0105-100 Operation of electrical systems Only original WOLF accessories may be used (electric coils, servomotors, etc.), otherwise WOLF cannot accept any liability. In addition, ÖVE regulations and the local building code apply to Austria.
  • Page 38 - Actuator, heating / cooling - Heating circuit pump / cooling circuit pump - As well as all other system-specific functions The WOLF warranty will be void if the function test is not carried out correctly. Fans Use tools to tightly seal the doors before commissioning (unit tightness), otherwise there is a risk of motor overload.
  • Page 39 17 Commissioning Electric reheating coil (accessory) To prevent the electric heating coil from switching off, never operate the CRL below its minimum air flow rate. Follow the relevant safety regulations for electric heating coils. The electric heating coil must be protected from moisture and water. Type 1300 2500...
  • Page 40 17 Commissioning Heat recovery function A rotating cylinder mass (rotor material corrosion-resistant aluminium alloy, with thermal wheel heat wound in corrugated and smooth layers) absorbs heat from the extract air flow exchanger and transfers it to the outdoor air. The rotor mass is sealed by a circumferential labyrinth seal.
  • Page 41 17 Commissioning Flow rate calculation The flow rate is calculated using the effective pressure method. This involves comparing the static pressure upstream of the inlet nozzle with the static pressure in the inlet nozzle. √Dp The flow rate can be calculated from the effective pressure Δp (differential pressure of the two static pressures) using the following equation.
  • Page 42 17 Commissioning CRL-3500 effective pressure The fans used for the CRL-3500 have a k value of 121. 950.0 V = 121 x √Dp 850.0 750.0 650.0 550.0 450.0 350.0 250.0 150.0 1500 1700 1900 2100 2300 2500 2700 2900 3100 3300 3500 3700...
  • Page 43 17 Commissioning CRL-6200 effective pressure The fans used for the CRL-6200 have a k value of 188. 1150.0 1050.0 V = 188 x √Dp 950.0 850.0 750.0 650.0 550.0 450.0 350.0 250.0 3000 3500 4000 4500 5000 5500 6000 6500 Flow rate [m³/h] Δp = effective pressure Δp...
  • Page 44 17 Commissioning CRL-11000 evo max effective The fans used for the CRL-11000 have a k value of 281. pressure 1600.0 1500.0 V = 281 x √Dp 1400.0 1300.0 1200.0 1100.0 1000.0 900.0 800.0 700.0 600.0 500.0 400.0 300.0 5000 6000 7000 8000 9000...
  • Page 45 17 Commissioning CRL-16500 evo max effective The fans used for the CRL-16500 have a k value of 281. pressure 950.0 850.0 V = (281 x √Dp ) x 2 750.0 650.0 550.0 450.0 350.0 250.0 150.0 7000 8250 9500 10750 12000 13250 14500...
  • Page 46: Maintenance Shutdown

    18 Maintenance shutdown Decommissioning Before starting any maintenance work, switch OFF the isolator and safeguard against unauthorised reconnection. If the isolator is switched back on unintentionally, maintenance staff or others in the vicinity could be at risk from rotating parts. Wait for the fans to come to a complete standstill before opening the doors (approx.
  • Page 47: Hygiene Checklist

    Check condensate pan for contamination, Clean and repair corrosion, damage and tightness Check the function of the drain and trap Clean and repair Repairs Only qualified personnel may remove faults or repair damage. Replace faulty components only with original WOLF spare parts. 3064361_201811...
  • Page 48: Maintenance

    20 Maintenance Fan motor unit Motor and bearing are maintenance-free. If necessary, clean the impeller with a soapy solution. Check that the test lead is seated firmly at the test connector on the inlet nozzle. Note Loose seating can result in faulty measurements. Electrical equipment - Regularly check the electrical equipment of the unit - Replace loose connections and faulty cables immediately...
  • Page 49 20 Maintenance electric coil (accessories) Check and clean at regular intervals. Cleaning the electric coils: - Vacuum, taking care not to bend the heating coils - Blast with compressed air, max. 1 bar If the cleaning pressure is too high, there is a risk of irreparable mechanical Note damage to the electric coils.
  • Page 50 20 Maintenance Servomotors on the dampers The motors are maintenance-free. At regular intervals, check that the connection from the servomotor to the damper drive is firmly seated. Condensate pan Regularly check the condensate pan for possible soiling and clean if required (see checklist).
  • Page 51: Notes

    21 Notes 3064361_201811...
  • Page 52 WOLF GmbH / Postfach 1380 / D-84048 Mainburg Tel. +49.0.87 51 74- 0 / Fax +49.0.87 51 74- 16 00 / www.WOLF.eu...