Wolf CRL Series Installation And Maintenance Instructions Manual page 45

Comfort ventilation unit with thermal wheel heat exchanger
Table of Contents

Advertisement

CRL-16500 evo max effective
pressure
Δp = effective pressure
(symbolic representation)
CRL-19500 evo max effective
pressure
Δp = effective pressure
(symbolic representation)
Further settings for the
BMK and accessories
3064361_201811
17 Commissioning
The fans used for the CRL-16500 have a k value of 281.
950.0
850.0
V = (281 x √Dp
750.0
650.0
550.0
450.0
350.0
250.0
150.0
7000
8250
9500
Δp
[Pa]
178
229
[m³/h] 7500 8500 9500 10500 11500 12500 13500 14500 15500 16500
V
The fans used for the CRL-19500 have a k value of 252.
1600.0
1400.0
V = (252 x √Dp
1200.0
1000.0
800.0
600.0
400.0
200.0
8000
9500
11000
Δp
[Pa]
268
355
[m³/h] 8250 9500 10750 12000 13250 14500 15750 17000 18250 19500
V
Further settings for the BMK programming unit can be found in the operating
instructions for the WRS-K control unit.
Accessories are installed in accordance with separate instruction manuals
which are provided with the relevant accessories.
) x 2
w
10750
12000
13250
Flow rate [m³/h]
286
349
419
495
) x 2
w
12500
14000
15500
Flow rate [m³/h]
455
567
691
828
14500
15750
17000
577
666
761
862
17000
18500
20000
977
1138
1311
1497
45