17 Commissioning
The fans used for the CRL-3500 have a k value of 121.
950.0
V = 121 x √Dp
850.0
750.0
650.0
550.0
450.0
350.0
250.0
150.0
1500
1700
1900
Δp
[Pa]
197
247
[m³/h] 1700 1900 2100 2300 2500 2700 2900 3100 3300 3500
V
The fans used for the CRL-4800 have a k value of 148.
1160.0
1060.0
V = 148 x √Dp
960.0
860.0
760.0
660.0
560.0
460.0
360.0
260.0
160.0
2000
2500
Δp
[Pa]
201
263
[m³/h] 2100 2400 2700 3000 3800 3600 3900 4200 4500 4800
V
w
2100
2300
2500
2700
2900
Flow rate [m³/h]
301
361
427
498
w
3000
3500
Flow rate [m³/h]
333
411
497
592
3100
3300
3500
3700
574
656
744
837
4000
4500
5000
694
805
924
1052
3064361_201811