Flow rate calculation
V
k
=
√Dp
w
V
in [m³/h] and Dp
CRL-1300 effective pressure
Δp = effective pressure
(symbolic representation)
CRL-2500 effective pressure
Δp = effective pressure
(symbolic representation)
3064361_201811
17 Commissioning
The flow rate is calculated using the effective pressure method. This involves
comparing the static pressure upstream of the inlet nozzle with the static
pressure in the inlet nozzle.
The flow rate can be calculated from the effective pressure Δp
(differential pressure of the two static pressures) using the following equation.
in [Pa]
The doors must be closed to determine the correct flow rate. Guide the test
w
hoses over the test connectors towards the outside.
The fans used for the CRL-1300 have a k value of 76.
320.0
270.0
220.0
170.0
120.0
70.0
20.0
450
Δp
[Pa]
[m³/h]
V
The fans used for the CRL-2500 have a k value of 77.
1110.0
1010.0
910.0
810.0
710.0
610.0
510.0
410.0
310.0
210.0
110.0
850
Δp
[Pa]
[m³/h]
V
V = 76 x √Dp
w
550
650
750
Flow rate [m³/h]
43
62
85
111
500
600
700
800
V = 77 x √Dp
w
1050
1250
1450
Flow rate [m³/h]
137
204
285
379
900
1100
1300 1500 1700 1900 2100 2300 2500
850
950
1050
1150
140
173
209
249
900
1000
1100
1200 1300
1650
1850
2050
2250
487
609
744
892
w
1250
1350
293
2450
2650
1054