Wolf CRL Series Installation And Maintenance Instructions Manual page 39

Comfort ventilation unit with thermal wheel heat exchanger
Table of Contents

Advertisement

Electric reheating coil (accessory) To prevent the electric heating coil from switching off, never operate the CRL
Condensate pan
Trap
3064361_201811
17 Commissioning
below its minimum air flow rate.
Follow the relevant safety regulations for electric heating coils.
The electric heating coil must be protected from moisture and water.
Type
Recomm. Minimum air
volume
Provide a trap for the condensate drain and route the condensate into the
sewerage system.
Protect the condensate drain from frost.
Fill the trap with water.
The effective height of the trap h (mm) must exceed the maximum underpressure
or overpressure at the condensate connector (1mm WC = 10Pa).
h = 1.5 x p (mmWC) + 50 mm (min.)
p
=
50 mm (WC) =
1.5
=
The trap drain line must not be connected directly to the public sewage system,
but rather must be able to run out freely. Vent longer drain lines to prevent
condensate backing up in the line (provide additional vent in trap drain line).
h
CRL
1300
m³/h
600
Under- or overpressure in mmWC according to appliance
design
Reserve (imprecision in design, evaporation)
Additional Safety factor
2500
3500
1200
1800
39