CRL-6200 effective pressure
Δp = effective pressure
(symbolic representation)
CRL-9000 effective pressure
Δp = effective pressure
(symbolic representation)
3064361_201811
17 Commissioning
The fans used for the CRL-6200 have a k value of 188.
1150.0
1050.0
V = 188 x √Dp
950.0
850.0
750.0
650.0
550.0
450.0
350.0
250.0
3000
3500
Δp
[Pa] 290
347
[m³/h] 3200 3500 3800 4100 4400 4700 5000 5300 5600 5900 6200
V
The fans used for the CRL-9000 have a k value of 240.
1500.0
1400.0
1300.0
V = 240 x √Dp
1200.0
1100.0
1000.0
900.0
800.0
700.0
600.0
500.0
400.0
300.0
200.0
3250
4500
Δp
[Pa] 278
352
[m³/h] 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000
V
w
4000
4500
5000
Flow rate [m³/h]
409
476
548
625
w
5750
7000
Flow rate [m³/h]
434
525
625
734
5500
6000
707
795
887
985 1088
8250
851
977
1111 1254 1406
6500
9500