ON/OFF Control Mode Setup:
-Set Point—Deviation High/Low
- Use UP/DOWN arrow keys to adjust the temperature value.
- Press the SELECT key to toggle between High and Low.
There will be a line below the active field.
- When complete, press MENU key to advance to screen # 7.
- Set Point—Deviation Band
Use UP/DOWN arrow keys to adjust the temperature value.
When complete, press the key to advance to screen # 7.
Screen # 7 - Setting Hysteresis Alarm
Use the UP/DOWN arrow keys to adjust value.
The user-defined value when the alarm will exit an alarm
condition. Example: The user has a Process High alarm programmed with a value of 150°C and
has set the Alarm Hysteresis of 1°C. The alarm has been activated after the temperature
reached 160°C. When temperature reaches 149°C, the alarm condition will not be active.
When complete, press MENU key to advance to screen # 8.
Screen # 8 - Setting Audible Alarm
Use UP/DOWN arrow keys to change value to either
ON audible alarm or OFF audible alarm.
When complete, press MENU key to advance to screen # 9.
Screen # 9 - Advanced Menu Gateway
Use UP/DOWN arrow keys to change selection to ENTER.
When complete, press MENU key to advance to screen # 10.
Screen # 10 - Calibration Gateway
Screen # 11 - Global Sensor Offset
Screen # 12 - Over Temperature Stop
Screen # 13 - Loop Break Stop
1.800.561.8187
19
www.
.com
Screen # 14 - Control Action
Screen # 15 - Control Mode
Screen # 16 - On/Off Control
Screen # 17 - Power Output Control
Screen # 18 - Run Time
information@itm.com
Need help?
Do you have a question about the TC9600 Advanced and is the answer not in the manual?
Questions and answers