Operating mode /
Designation
order code
Steam/Water Energy
12)
Energy flow of steam / hot water.
/ NS3
The calculation is done in
accordance with IAPWS-IF97.
3) The connection via the analog input or HART input is described in the chapter titled "Electrical connections" on page 29.
5) The highest priority of the device is to record the temperature via the analog input, as long as the analog input is activated as a temperature input. If the analog input is
not available as a temperature input, the system attempts to record the temperature via the HART input. If both the analog input and the HART input are deactivated
as a temperature input, the system uses the default density value.
6) The highest priority of the device is to record the pressure via the analog input, as long as the analog input is activated as a pressure input. If the analog input is not
available as a pressure input, the system attempts to record the pressure via the HART input. If both the analog input and the HART input are deactivated as a
pressure input, the system uses the default pressure value.
13) Two different properties of steam are supported: saturated steam and overheated steam. The end user can change this in the Device Setup / Plant/Customized /
Compensation Setting -> Water/Steam Type menu item.
14) Required only for net energy calculation of the actually consumed energy
Change from one to two columns
Additional parameters required
Energy calculation
13)
Measuring medium temperature
upstream
14)
Measuring medium temperature
downstream
14)
Operating pressure
3) 6)
Operating temperature
3) 5)
VortexMaster FSV430, FSV450 SwirlMaster FSS430, FSS450 | CI/FSV/FSS/430/450-EN Rev. G 51
Parameter setting
Selection of the type of energy calculation via:
Device Setup / Plant/Customized /
Compensation Setting Energy calc. method
With internal temperature sensor.
No information required, the measured value
from the temperature sensor is used.
Default setting for the temperature value:
Device Setup / Plant/Customized /
Compensation Setting -> Preset Int.Temp
Via analog input:
Input/Output / Field Input / Analog In Value ->
Temperature
Via HART input:
Input/Output / Field Input / HART In Value ->
Temperature
Default setting for the temperature:
Device Setup / Plant/Customized /
Compensation Setting -> Preset Ext.Temp
Via analog input:
Input/Output / Field Input / Analog In Value ->
Pressure
Via HART input:
Input/Output / Field Input / HART In Value ->
Pressure
Default setting for the pressure value:
Device Setup / Plant/Customized /
Compensation Setting -> Preset
Pressure(abs)
With internal temperature sensor.
No information required, the measured value
from the temperature sensor is used.
Default setting for the temperature value:
Device Setup / Plant/Customized /
Compensation Setting -> Preset Int.Temp