Operating mode /
Designation
order code
Gas Power / NG4
Energy measurement
(gaseous measuring media)
Bio Act. Volume / NG5
Partial operating volume flow rate
of biogas
9)
Bio Std/Norm Vol.
/
Partial standard volume flow of
NG6
biogas
Steam Act. Volume / NS1 Actual volume flow rate of steam
Steam/Water Mass
Mass flow rate of steam / hot
(internal density
water.
determination)
10)
/ NS2
The calculation is done in
accordance with IAPWS-IF97.
Steam/Water Mass
Mass flow rate of steam / hot
(external density
water
determination)
11)
/ NS2
2) The highest priority of the device is to record the density via the analog input, as long as the analog input is activated as a density input. If the analog input is not
available as a density input, the system attempts to record the density via the HART input. If both the analog input and the HART input are deactivated as a density
input, the system uses the default density value.
3) The connection via the analog input or HART input is described in the chapter titled "Electrical connections" on page 29.
5) The highest priority of the device is to record the temperature via the analog input, as long as the analog input is activated as a temperature input. If the analog input is
not available as a temperature input, the system attempts to record the temperature via the HART input. If both the analog input and the HART input are deactivated
as a temperature input, the system uses the default density value.
6) The highest priority of the device is to record the pressure via the analog input, as long as the analog input is activated as a pressure input. If the analog input is not
available as a pressure input, the system attempts to record the pressure via the HART input. If both the analog input and the HART input are deactivated as a
pressure input, the system uses the default pressure value.
8) The biogas proportion can be determined via the analog input, HART input or default setting. The highest priority of the device is to record the biogas proportion via
the analog input, as long as the analog input is activated as a biogas proportion input. If the analog input is not available as a biogas proportion input, the system
attempts to record the biogas proportion via the HART input. If both the analog input and the HART input are deactivated as a biogas proportion input, the system
uses the default biogas proportion value.
9) In order to implement the "Bio Std/Norm Vol." mode, as a precondition the required parameters from one of the NG2 modes must be available.
10) In order to implement the "Steam/Water Mass" mode with internal density determination, the selection "Calculated from..." must be set in the Device Setup /
Plant/Customized / Compensation Setting -> Density Selection menu.
11) In order to implement the "Steam/Water Mass" mode with external density determination, in the menu Device Setup / Plant/Customized / Compensation Setting ->
Density Selection the selection "Ext. Density" must be made.
50 CI/FSV/FSS/430/450-EN Rev. G | VortexMaster FSV430, FSV450 SwirlMaster FSS430, FSS450
Additional parameters required
Energy density
Biogas proportion
8)
n/a
Steam type
Operating pressure
3) 6)
Operating temperature
3) 5)
Operating density
2) 3)
Parameter setting
Device Setup / Plant/Customized /
Compensation Setting -> Gas Energy Density
Via analog input:
Input/Output / Field Input / Analog In Value ->
Gas Content
Via HART input:
Input/Output / Field Input / HART In Value ->
Gas Content
Default setting for the density:
Device Setup / Plant/Customized /
Compensation Setting -> Preset Density
Selection of steam type via:
Device Setup / Plant/Customized /
Compensation Setting / Water/Steam Type
Via analog input:
Input/Output / Field Input / Analog In Value ->
Pressure
Via HART input:
Input/Output / Field Input / HART In Value ->
Pressure
Default setting for the pressure value:
Device Setup / Plant/Customized /
Compensation Setting -> Preset
Pressure(abs)
With internal temperature sensor.
No information required, the measured value
from the temperature sensor is used.
Default setting for the temperature value:
Device Setup / Plant/Customized /
Compensation Setting -> Preset Int.Temp
Via analog input:
Input/Output / Field Input / Analog In Value ->
Density
Via HART input:
Input/Output / Field Input / HART In Value ->
Density
Default setting for the density:
Device Setup / Plant/Customized /
Compensation Setting -> Preset Density