EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
Table 5.1 Specifications on Required Components for (1) to (4) Functions
Component
Auxiliary Relay (X1, X2)
Changeover Switch (SS2, SS3)
3P Connector Cord
Cord (Indoor)
Cord (Outdoor)
NOTE:
1. Make the wires CN3 as short as possible. Do not install the wires with the 220V power line. Install them
more than 12 in. (30cm) away from each other. (Intersecting them is acceptable.)
If the wires are installed along the power line, comply with the following points to prevent noise.
a. Pass either of the low voltage wire and 220V power line through a metal conduit tube and ground one
end.
b. Use a shielded wire for a low voltage wire and ground one end.
The maximum wiring length is 230 ft. (70m).
2. When using this function, it is recommended that safety devices such as an electric leakage breaker or
smoke detector, etc., be used because this is an unattended function.
5-10
Manufacturer or Specifications
OMRON Mini Power Relay
Model: MY1F/2F or Equivalent
Manual Type
Optional Part PCC-1A
(Connectable to JST Connector XARP-3), 12V
Low Voltage
AWG22 (0.3mm
220V Class
AWG20 or AWG18 (0.5 to 0.75mm
Low Voltage
AWG20 or AWG18 (0.5 to 0.75mm
220V Class
AWG14 (2mm
2
)
2
)
2
)
2
)
Remarks
Voltage 220V
Five Cords with
Connectors as One Set
less than 12V
less than 12V
SM-16005-rev.2