(7) Fixing of Operation as Exclusive Cooling Unit (b7)
This function is utilized when exclusive cooling operation is required.
This function invalidates the heating operation and the automatic COOL/HEAT operation, as the
operation of exclusive cooling unit.
(8) Automatic COOL/HEAT Operation (b8)
This function is utilized to change cooling and heating operation automatically (the same operation
mode for indoor units in the same refrigerant cycle).
This function is invalid when the outdoor unit is cooling-only model or the function of "Fixing of
Operation as Exclusive Cooling Unit" is valid.
NOTES:
● This function is not available for all fresh mode and gas sensor mode.
● Depending on the operation range the compressor may stop and this unit switches to fan mode
during heating or cooling operation.
● Function (36) "Damper Minimum Opening (d7)" should be set to "00" for this function. Higher step
may increase the load and affect the air outlet temperature of other standard indoor units.
(9) Fixing of Fan Speed (b9)
This function is utilized to fix the fan speed.
When this function is valid, the fan speed can not be changed by the wired controller.
(10) Not Prepared (bA)
(11) Cooling Temperature Compensation due to Uneven Heat Load (bb)
This function is utilized to provide the longer cooling operation time than the standard.
When this function is valid, Thermo-ON/OFF is controlled under the lower temperature conditions than
the setting temperature (the indicated value) of the wired controller.
Setting Temperature for Room Temperature Control during Cooling
Setting Condition
00 (Standard)
01
02
NOTE:
The minimum setting temperature after correction is 66
(12) Not Prepared (bC)
(13) Not Prepared (bd)
(14) Not Prepared (bE)
(15) Not Prepared (C1)
(16) Not Prepared (C2)
(17) Not Prepared (C3)
(18) Not Prepared (C4)
(19) EconoFresh Pressure Mode (C5)
This is the setting for Ducted (Medium Static) with EconoFresh Kit which must be set before use.
(20) Hi Speed during Heating Thermo-OFF (C6)
This function is utilized to increase the fan speed during heating Thermo-OFF with the function (19). (The
fan speed does not increase during heating Thermo-OFF even if the function (19) is valid.)
(21) Canceling of Enforced 3 Minutes Minimum Operation Time of Compressor (C7)
The compressor operation is enabled for a minimum of 3 minutes when operation is started by the
"Enforce 3 Minutes Minimum Operation Time of Compressor". This function is utilized to cancel
the function "Enforced 3 Minutes Minimum Operation Time of Compressor" (Enforced 3 Minutes
Compressor Guard).
NOTE:
The compressor operation is stopped immediately as following conditions.
● The protection device is activated.
● The operation stop button is pressed.
SM-16005-rev.2
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
Actual Control Temperature
Wired Controller Setting Temperature (Indicated Value)
Wired Controller Setting Temperature (Indicated Value) -2
Wired Controller Setting Temperature (Indicated Value) -3
o
F (-1
o
F (-2
o
o
F (19
C).
o
C)
o
C)
5-25